Emerson PACMotion VFD Series User Manual page 86

Ac variable speed drive
Hide thumbs Also See for PACMotion VFD Series:
Table of Contents

Advertisement

Table 59: 500 – 600 Volt (+ / - 10%), 3 Phase Input, 3 Phase Output
Frame
Power
Input
Size
Rating
Current
kW
HP
A
2
0.75 1
2.5
2
1.5
2
3.7
2
2.2
3
4.9
2
4
5
7.8
2
5.5
7.5
10.8
3
7.5
10
14.4
3
11
15
20.6
3
15
20
26.7
4
18.5 25
34
4
22
30
41.2
4
30
40
49.5
5
37
50
62.2
5
45
60
75.8
6
55
75
90.9
6
75
100
108.2
6
90
125
127.7
6
110
150
160
NOTE
• Ratings shown above apply to 40°C Ambient temperature. For derating information, refer to section Table
62: Derating for Ambient Temperature
• The drive is protected against short-circuit from power output to protective earth for all rated cable
lengths, cable sizes and cable types.
• 3 phase drive can be connected to single phase supply when the output current is 50% derated.
• The maximum cable lengths stated here are based on hardware limitations and do NOT take into
consideration any requirements for compliance to any EMC standards. Please see section for further
information.
• The maximum motor cable length stated applies to using a shielded motor cable. When using an
unshielded cable, the maximum cable length limit may be increased by 50%. When using the Emerson
recommended output choke, the maximum cable length may be increased by 100%.
• The PWM output switching from any inverter when used with a long motor cable length can cause an
increase in the voltage at the motor terminals, depending on the motor cable length and inductance. The
rise time and peak voltage can affect the service life of the motor. Emerson recommend using an output
choke for motor cable lengths of 50m or more to ensure good motor service life.
• For IP20 Frame Size 8 the Vector Speed and Torque control modes may not operate correctly with
long motor cables and output filters. It is recommended to operate in V/F mode only for cable lengths
exceeding 50m.
• Supply and motor cable sizes should be dimensioned according to local codes or regulations in the
country or area of installation.
• For UL compliant installation, use use only with copper stranded conductors rated 75degC, UL Class CC or
Class J Fuses (exception: Eaton Bussmann FWP series must be used for size 6A & 6B IP20 models).
86
Fuse or MCB
Maximum Cable
(Type B)
Size
Non UL UL
mm AWG/kcmil
10
6
8
10
6
8
10
10
8
10
10
8
16
15
8
16
20
8
25
30
8
32
35
8
40
45
16
50
60
16
63
70
16
80
80
35
100
100
35
125
125
150
125
150
150
160
175
150
200
200
150
PACMotion VFD AC Variable Speed Drive User Guide
Rated Output
Current
A
8
2.1
8
3.1
8
4.1
8
6.5
8
9
8
12
8
17
8
22
5
28
5
34
5
43
2
54
2
65
300MCM
78
300MCM
105
300MCM
130
300MCM
150
Maximum Motor
Recommended
Cable Length
Brake Resistance
m
ft
Ω
100
330
600
100
330
300
100
330
200
100
330
150
100
330
100
100
330
80
100
330
50
100
330
33
100
330
33
100
330
22
100
330
22
100
330
16
100
330
12
100
330
12
100
330
8
100
330
8
100
330
8
GFK-3111A