Par
Parameter Name
P2-13
Analog output AO2 function
Digital Output Mode. Logic 1 = +24 V DC
0
Drive running
1
Drive healthy
2
At speed
3
Motor speed > 0
4
Motor speed >= limit
5
Motor current >= limit
6
Motor torque >= limit
7
Analog input 2 >= limit
Note When using settings 4 – 7, parameters P2-19 and P2-20 must be used together to control the behaviour.
The output will switch to Logic 1 when the selected signal exceeds the value programmed in P2-19, and
return to Logic 0 when the signal falls below the value programmed in P2-20.
Analog Output Mode
8
Motor speed
9
Motor current
10
Motor torque
11
Motor power
12
PID output
P2-14
Analog output AO2 format
0-10 volt 0 to10 V
10-0 volt 10 to 0 V
0-20 mA 0 to 20 mA
20-0 mA 20 to 0 mA
4-20 mA 4 to 20 mA
20-4 mA 20 to 4 mA
P2-15
Relay 1 function
Setting
Function
0
Drive running
1
Drive healthy
2
At speed
3
Motor speed > 0
4
Motor speed >= limit
5
Motor current >= limit
6
Motor torque >= limit
7
Analog input 2 >= limit
8
Reserved
9
Reserved
10
Maintenance due
11
Drive ready to run
12
Drive tripped
13
STO status
14
PID error >= limit
Note When using settings 4 – 7 and 14, parameters P2-16 and P2-17 must be used together to control the
behaviour. The output will switch to Logic 1 when the selected signal exceeds the value programmed in
P2-16, and return to Logic 0 when the signal falls below the value programmed in P2-17.
P2-16
Relay 1 / AO1 upper limit
P2-17
Relay 1 / AO1 lower limit
Used in conjunction with some settings of Parameters P2-11 & P2-15.
GFK-3111A
Logic 1 when the PACMotion VFD is enabled (Running).
Logic 1 When no Fault condition exists on the drive.
Logic 1 when the output frequency matches the setpoint frequency.
Logic 1 when the motor runs above zero speed.
Logic 1 when the motor speed exceeds the adjustable limit.
Logic 1 when the motor current exceeds the adjustable limit.
Logic when the motor torque exceeds the adjustable limit.
Logic when the signal applied to the Analog Input 2 exceeds the
adjustable limit.
0 to P1-01.
0 to 200% of P1-08.
0 to 200% of motor rated torque.
0 to 150% of drive rated power.
Output from the internal PID Controller, 0 – 100%.
Logic 1 when
The PACMotion VFD is enabled (Running).
No fault or trip condition exists on the drive.
Output frequency matches the setpoint frequency.
The motor runs above zero speed.
The motor speed exceeds the adjustable limit.
The motor current exceeds the adjustable limit.
The motor torque exceeds the adjustable limit.
The signal applied to the Analog Input 2 exceeds the adjustable limit.
No Function.
No Function.
The internally programmable maintenance timer has elapsed.
0 to 150% of drive rated power.
The drive is not tripped, the STO circuit is closed, the mains supply is
present and the hardware enable input present (Digital Input 1 unless
changed by the user).
When both STO inputs are present and the drive is able to be operated.
The PID Error (difference between setpoint and feedback) is greater than
or equal to the programmed limit.
PACMotion VFD AC Variable Speed Drive User Guide
Minimum
Maximum Default
0
12
See Below
0
14
P2-17
200.0
0.0
P2-16
Units
9
-
0-10 Volt
-
1
-
100.0
%
0.0
%
57