Table 18: Control Connections
Key
1
+24 V DC
24 Volt DC Input / Output
2
DI 1
Digital Input 1 (Run Enable)
3
DI 2
Digital Input 2
4
DI 3
Digital Input 3
5
+10 V DC
+10 Volt DC Output
6
AI 1 / DI 4
Analog Input 1 / Digital Input 4
7
0V / COM
0 Volt Common
8
AO 1
Analog Output 1
9
0V / COM
0 Volt Common
10
AI 2 / DI 5
Analog Input 2 / Digital Input 5
11
AO2
Analog Output 2
12
STO+
STO + 24 V DC Connection
13
STO-
STO 0 Volt Connection
14
RL1-COM
Auxiliary Relay Output 1 Common
15
RL1-NO
Auxiliary Relay Output 1 Normally Open Drive Healthy
16
RL1-NC
Auxiliary Relay Output 2 Normally Closed Drive Faulty
17
RL2-A
Auxiliary Relay Output 2
18
RL2-B
Auxiliary Relay Output 2
NOTE
Digital Inputs: Logic High = 8-30 V DC (30 V DC max)
Analog Outputs: 0 – 10 Volt / 4-20 mA (20 mA max)
SAFE TORQUE OFF input: Logic High = 18-30 V DC (Also refer to section Safe Torque Off)
GFK-3111A
PACMotion VFD AC Variable Speed Drive User Guide
Default Function
Open
Closed
On-board +24 V DC Supply (100 mA)
or External 24 V DC Input
STOP
RUN
FORWARD
REVERSE
P1-12 Reference
Preset Speeds
On-board +10 V DC Supply (10 mA)
Speed Reference 1 (0-10 V)
0V Common for AI/AO/DI/DO
Motor Speed (0-10 V)
0V Common for AI/AO/DI/DO
P2-01 Speed Ref.
P2-02 Speed Ref.
Motor Current (0-10 V)
InHibit
Run Permit
Drive Faulty
Drive Healthy
Drive Stopped
Drive Running
Sec .
Page
4.10.1 32
4.10.2 32
4.10.2 32
4.10.2 32
4.10.3 32
4.10.4 33
4.10.3 32
4.10.4 33
4.14
36
4.10.5 33
4.10.5 33
4.10.5 33
4.10.5 33
4.10.5 33
31