Vimar 02952 Installer Manual page 9

Knx touch thermostat.
Table of Contents

Advertisement

Thermostat
Communication objects and ETS parameters
Continued
No.
ETS name
Function
35
Heating Valve
A: Valve
Thermostat A: Second Stage
36
Cooling Valve
A: 2
36
Cooling Valve
A: 2
37
Heating Valve
A: 2
37
Heating Valve
A: 2
Thermostat A: Fan
38
Proportional (0- 100%) A: Fan Inputs
39
NOT USED
40
V1 speed
A: Fan Inputs
41
V2 speed
A: Fan Inputs
42
V3 speed
A: Fan Inputs
43
Automatic
A: Fan Inputs
44
Proportional (0- 100%) A: Fan Outputs
45
Off
A: Fan Outputs
46
V1 speed
A: Fan Outputs
47
V2 speed
A: Fan Outputs
48
V3 speed
A: Fan Outputs
49
V1 speed
A: Fan Disable
50
V2 speed
A: Fan Disable
51
V3 speed
A: Fan Disable
Thermostat A: Window
52
Window Sensor
A: Window
Continued
Description
If the "Valve" parameter is set for 4-pipe proportional
systems for Winter valve management: to be used to
control the head of a radiating system or for the propor-
tional valve of a fan coil
If second cooling stage is enabled to be used for the
Cooling Stage
nd
boost function (cooling) for on/off valve control
If second cooling stage is enabled to be used for the
Cooling Stage
nd
boost function (cooling) for proportional valve control
If second heating stage is enabled to be used for the
Heating Stage
nd
boost function (heating) for on/off valve control
If second heating stage is enabled to be used for the
Heating Stage
nd
boost function (heating) for proportional valve control
Used to set a proportional speed for the fan coil fan (if
the selected fan is proportional with 3 speeds) via a su-
pervisor (e.g., touch screen)
Used to force activation of fan coil speed V1 (if the
selected fan has 3 speeds)
Used to force activation of fan coil speed V2 (if the
selected fan has 3 speeds)
Used to force activation of fan coil speed V3 (if the
selected fan has 3 speeds)
Used to force activation of fan coil speed AUTO (if the
selected fan has 3 speeds)
Used to read the proportional speed of the fan coil fan
(if the selected fan is proportional with 3 speeds with the
8-Bit Object - Proportional (0-100%). This object is used
for controlling proportional actuators.
Used to read the deactivation status of all 3 speeds (if
the selected fan has 3 speeds). The thermostat sends a
1 bit when the fan is off (fan coil speed 0).
This is the object to pair with the relay of speed 1 of the
fan coil (to read the status of speed V1 of the fan coil,
this object can be polled by the bus)
This is the object to pair with the relay of speed 2 of the
fan coil (to read the status of speed V2 of the fan coil,
this object can be polled by the bus)
This is the object to pair with the relay of speed 3 of the
fan coil (to read the status of speed V3 of the fan coil,
this object can be polled by the bus)
To disable speed V1 (if the selected fan has 3 speeds)
To disable speed V2 (if the selected fan has 3 speeds)
To disable speed V3 (if the selected fan has 3 speeds)
Object to be paired with the input to which a win-
dow-contact is connected so that the thermostat
switches to OFF-PROTECTED when the window is
opened, depending on whether the mode is Air Condi-
tioning or Heating
C = Communication; R = Read; W = Write; T = Transmission; U = Enable update
Flag 1
Type
Priority
C R W T U
I
1 byte
C
R
-
T
-
- Low
1 bit
C
R
-
T
-
- Low
1 byte
C
R
-
T
-
- Low
1 bit
C
R
-
T
-
- Low
1 byte
C
R
-
T
-
- Low
1 byte
C
- W -
U
- Low
1 bit
C
- W -
U
- Low
1 bit
C
- W -
U
- Low
1 bit
C
- W -
U
- Low
1 bit
C
- W -
U
- Low
1 byte
C
R
-
T
-
- Low
1 bit
C
R
-
T
-
- Low
1 bit
C
R
-
T
-
- Low
1 bit
C
R
-
T
-
- Low
1 bit
C
R
-
T
-
- Low
1 bit
C
R W T U
- Low
1 bit
C
R W T U
- Low
1 bit
C
R W T U
- Low
1 bit
C
- W -
U
- Low
9