Vimar 02952 Installer Manual page 12

Knx touch thermostat.
Table of Contents

Advertisement

Thermostat
Communication objects and ETS parameters
Continued
No.
ETS name
Function
88
V2 speed
B: Fan Inputs
89
V3 speed
B: Fan Inputs
90
Automatic
B: Fan Inputs
91
Proportional (0- 100%) B: Fan Outputs
92
Off
B: Fan Outputs
93
V1 speed
B: Fan Outputs
94
V2 speed
B: Fan Outputs
95
V3 speed
B: Fan Outputs
96
V1 speed
B: Fan Disable
97
V2 speed
B: Fan Disable
98
V3 speed
B: Fan Disable
Thermostat B: window
99
Window Sensor
B: Window
Thermostat B: scenario
100
Scenario
B: Scenario
Thermostat B: Auto/Man
Temperature: Automat-
101
B: Manual operation
ic/Manual
Fan coil: Automatic/
102
B: Manual operation
Manual
Temperature: Disable
103
B: Manual operation
Local operation
Fan coil: Disable Local
104
B: Manual operation
Operation
Thermostat B: Floor Probe Alarm
105
Floor Temperature
B: Alarm
GLOBAL
106
Initialisation
Alarm
107
NOT USED
Continued
12
Description
Used to force activation of fan coil speed V2 (if the
selected fan has 3 speeds)
Used to force activation of fan coil speed V3 (if the
selected fan has 3 speeds)
Used to force activation of fan coil speed AUTO (if the
selected fan has 3 speeds)
Used to read the proportional speed of the fan coil fan (if
the selected fan is proportional or 8-bit with 3 speeds).
This object is used for controlling proportional actuators.
Used to read the deactivation status of all 3 speeds (if
the selected fan has 3 speeds). The thermostat sends a
1 bit when the fan is off (fan coil speed 0).
This is the object to pair with the relay of speed 1 of the
fan coil (to read the status of speed V1 of the fan coil,
this object can be polled by the bus)
This is the object to pair with the relay of speed 2 of the
fan coil (to read the status of speed V2 of the fan coil,
this object can be polled by the bus)
This is the object to pair with the relay of speed 3 of the
fan coil (to read the status of speed V3 of the fan coil,
this object can be polled by the bus)
To disable speed V1 (if the selected fan has 3 speeds)
To disable speed V2 (if the selected fan has 3 speeds)
To disable speed V3 (if the selected fan has 3 speeds)
Object to be paired with the input to which a win-
dow-contact is connected so that the thermostat
switches to OFF-PROTECTED when the window is
opened, depending on whether the mode is Air Condi-
tioning or Heating
To activate a scenario with a 1 Byte message
To see whether the guest has altered the thermostat
temperature setpoint with respect to the default setting
To see whether the guest has altered the fan coil speed
with respect to the default setting
Activating this object prevents the guest from altering
the setpoint temperature by means of the thermostat
buttons with respect to the value set by the bus
Activating this object prevents the guest from altering
the fan coil speed by means of the thermostat buttons
with respect to the value set by the bus
If the temperature limitation is active an alarm is sent
when the temperature exceeds the set threshold
Do not use: it is used for automatic testing during
production of the device
C = Communication; R = Read; W = Write; T = Transmission; U = Enable update
Flag 1
Type
Priority
C R W T U
I
1 bit
C
- W -
U
- Low
1 bit
C
- W -
U
- Low
1 bit
C
- W -
U
- Low
1 byte
C
R
-
T
-
- Low
1 bit
C
R
-
T
-
- Low
1 bit
C
R
-
T
-
- Low
1 bit
C
R
-
T
-
- Low
1 bit
C
R
-
T
-
- Low
1 bit
C
R W T U
- Low
1 bit
C
R W T U
- Low
1 bit
C
R W T U
- Low
1 bit
C
- W -
U
- Low
1 byte
C
- W -
U
- Low
1 bit
C
R
-
T
-
- Low
1 bit
C
R
-
T
-
- Low
1 bit
C
- W -
U
- Low
1 bit
C
- W -
U
- Low
1 bit
C R -
T -
-
Low
1 bit
C
R
-
T
-
- Low