Vimar 02952 Installer Manual page 16

Knx touch thermostat.
Table of Contents

Advertisement

Thermostat
Communication objects and ETS parameters
Backlighting
Backlighting Parameters
Values available
ETS text
[ Default value ]
0 = Off
1 = ON push button
Backlighting
2 =Ecometer Mode
[ 1 ]
When Backlighting is set to "Ecometer Mode" the display
backlighting colour indicates the expected consumption
provided by the Ecometer with the background colour.
CAUTION: We do not recommend using the Ecometer view
when the thermostat is set to neutral zone mode as the
colour of the display depends on the active setpoint and
the information for the end user might not be clear.
Digital Input
Digital Input Parameters
Values available
ETS text
[ Default value ]
0 = General Use
Input Function
1 = Window Sensor
[ 0 ]
0 = Switching on Rising
Edge
1 = Toggle on Rising
Edge
2 = Switching on Falling
Edge
Function (for gener-
al use)
3 = Toggle on Falling
Edge
4 = Status Send
[ 0 ]
0 = Deactivated
Window Sensor
1 = Normally Open
Mode (for thermo-
stat-A and thermo-
2 = Normally Closed
stat-B)
[ 0 ]
16
Comment
Always off
On when pressing the touch
buttons.
Note: after some time of
inactivity, the backlighting
turns off.
Ecometer Mode on
Comment
If set as "General use", it
also sends 0/1 over the bus
towards a supervisor
Rising edge = close contact
Falling edge = open contact
Switching = sends a 1 bit
value (On/Off) on opening
and the opposite on closing
Toggle = on every defined
edge (opening or closure),
On and then Off is sent to
the cycle
To send the contact status
upon each switching and
also cyclically.
Defines whether the window
sensor is normally open or
closed.
Backlighting Off
Ecometer Mode
Backlighting On
Default colours
Colour customisation
Digital Input - Window Sensor
Digital Input - General Use