Page 3
GENERAL CHARACTERISTICS AND FUNCTIONS from page 5 COMMUNICATION OBJECTS AND ETS PARAMETERS from page 7 from page 31...
Page 4
For all the details about the Well-contact Plus system, refer to the installer manual that can be downloaded from the Software Product Software Well-contact Plus section of the website: www.vimar.com.
Page 5
Fan coil Ambient Setpoint decrease speed humidity button 02952 Heating with boost function General characteristics The thermostat is suitable for controlling room temperature Air-conditioning with boost function (heating/air-conditioning) in 2 or 4 pipe systems (heating/air- conditioning) and neutral zone (only in 4-pipe systems), with Temperature display and thermostat B menu the "boost"...
Page 6
Thermostat General characteristics and functions Neutral zone The KNX 02952 thermostat is configured in Neutral Zone mode if the following object is NOT connected: "Enable A: Summer - The "Neutral Zone" is an operating mode of the thermostat (only Winter – control" or "Enable B: Summer - Winter – control".
Page 7
Thermostat Communication objects and ETS parameters List of existing communication objects and standard settings Flag 1 ETS name Function Description Type Priority C R W T U To see the temperature read by the thermostat sensor (to see the temperatures measured by thermostats A/B Internal sensor Internal probe temperature 2 byte...
Page 8
Thermostat Communication objects and ETS parameters Continued Flag 1 ETS name Function Description Type Priority C R W T U To read the seasonal mode set on the thermostat (0 = Status A: Summer - Winter - status 1 bit - Low Summer, 1 = Winter) To set the seasonal mode on the thermostat (1 = Win-...
Page 9
Thermostat Communication objects and ETS parameters Continued Flag 1 ETS name Function Description Type Priority C R W T U If the "Valve" parameter is set for 4-pipe proportional systems for Winter valve management: to be used to Heating Valve A: Valve 1 byte - Low...
Page 10
Thermostat Communication objects and ETS parameters Continued Flag 1 ETS name Function Description Type Priority C R W T U Thermostat A: Scenario Scenario A: Scenario To activate a scenario with a 1 Byte message 1 byte - W - - Low Thermostat A: Auto/Man Temperature: Automat-...
Page 11
Thermostat Communication objects and ETS parameters Continued Flag 1 ETS name Function Description Type Priority C R W T U Winter Comfort B: Setpoint - status, control To read and set the Winter Comfort setpoint. 2 byte R W T U - Low Winter Standby B: Setpoint - status, control...
Page 12
Thermostat Communication objects and ETS parameters Continued Flag 1 ETS name Function Description Type Priority C R W T U Used to force activation of fan coil speed V2 (if the V2 speed B: Fan Inputs 1 bit - W - - Low selected fan has 3 speeds) Used to force activation of fan coil speed V3 (if the...
Page 13
Thermostat Communication objects and ETS parameters Continued Flag 1 ETS name Function Description Type Priority C R W T U NOT USED Used for viewing, on the thermostat display, the trigger- General Alarm 1 bit C R - ing of a generic alarm on the KONNEX BUS Input Input Device IN control...
Visibility of operating bling the operating modes mode setting button on the display CAUTION: If you use thermostats art. 02952 with firmware [ Yes ] version 1.00 do not use the setting: Percentage displayed = Humidity. Possibility of disa- Heating icon visible...
Page 15
Thermostat Communication objects and ETS parameters Value Enable Menu=Enable Enable Menu=Enable Enable Menu=Disable Displayed Button Activation = Enable Button Activation = Disable Button Activation = Enable Display Current Temperature Setpoint Current Display Off View Difference Setpoint Note: In "View Setpoint Difference" mode, the difference between the Setpoint set via configuration by ETS and the Setpoint modified locally by the user is displayed.
Page 16
Thermostat Communication objects and ETS parameters Backlighting Backlighting Parameters Backlighting Off Values available ETS text Comment [ Default value ] 0 = Off Always off On when pressing the touch Ecometer Mode buttons. 1 = ON push button Note: after some time of Backlighting inactivity, the backlighting turns off.
Values available ETS text Comment [ Default value ] For the thermostat's internal 0... 100 sensor, the Vimar wired NTC probe (if present) and the KNX Temperature sen- probes, this determines the sor weightings relative importance for calcu- [ 0 ]...
Thermostat Communication objects and ETS parameters Setpoint (A/B) Setpoint parameters Values available ETS text Comment [ Default value ] 1 = Comfort 2 = Standby 3 = Energy saving Mode at bus power Thermostat operating mode at bus power on 4 = Protect 255 = Last Mode Selected...
Thermostat Communication objects and ETS parameters Temperature Setpoint (A/B) Sensor parameters Continued Values available Values available ETS text Comment ETS text Comment [ Default value ] [ Default value ] Winter Comfort Setpoint See "Range" table [20] If you set "On" you can set the Winter Standby Setpoint [18]...
Thermostat Communication objects and ETS parameters Window sensor (A/B) Sensor parameters Values available ETS text Comment [ Default value ] 0 = Off Sets the time delay that Window sensor heating/air conditioning 8 = 120 sec. delay stops after window open detection [ 4 = 30 ] Window sensor (A/B)
Thermostat Communication objects and ETS parameters Proportional/Integral (PI) control Continuous integral proportional: PI control with proportional valve This type of control uses a more advanced algorithm that keeps the temperature inside the room more stable, increasing comfort. This algorithm works by switching the system on and off so as to be like a gradual increase or decrease in the system's thermal (or refrigerating) power.
Page 22
Thermostat Communication objects and ETS parameters Continued Values available ETS text Comment [ Default value ] 5 min. 6 min. 7 min. Integral band (A/B) 8 min. 9 min. 10 min. 12 min. 15 min. 17 min. Integral Cooling Value 20 min.
Page 23
Thermostat Communication objects and ETS parameters Valve (A/B) Valve parameters Values available ETS text Comment [ Default value ] 0 = 2-Pipe Circuit On/ 2-Pipe Circuit On/Off (A/B) 1 = 4-Pipe Circuit On/ Select according to the type System Layout of installed system 2 = 2-Pipe Proportional 3 = 4-Pipe Proportional...
Page 24
Thermostat Communication objects and ETS parameters Heating/Cooling Stage (A/B) "Boost" The second stage is used to control a second heating or cooling source that allows the "boost" function. The "boost" function enables the second auxiliary source when the Stage Disabled (A/B) current temperature differs from the current setpoint by more than the set threshold.
Thermostat Communication objects and ETS parameters Fan (A/B) Fan parameters Continued Values available Values available ETS text Comment ETS text Comment [ Default value ] [ Default value ] No thermostat controlled fan coil. Disables the graphics for Duration of "Manual Forcing" 0 = Off the fan on the thermostat for the fan speed if the guest...
Page 26
Thermostat Communication objects and ETS parameters Manual operation of the fans The user selects the speed used by the thermostat only when the valve is on; if the valve is off at the time of selection, the thermostat saves the setting and uses it again the next time the valve is on.
Page 27
Thermostat Communication objects and ETS parameters Proportional fan coil operation Proportional fan operation is similar to that of the three-speed fan coil. When the valve is OFF the proportional speed is equal to 0%; when the valve is ON the value of the proportional speed depends on the difference between the setpoint and the temperature measured in the room.
Page 28
Thermostat Communication objects and ETS parameters Scenario (A/B) 16 scenarios are available. 16 different scenarios can therefore be saved on the device output. With Enable Scenario Learning you can also set the status of the output for the desired scenario with a message from the bus (scene learn). Scenario parameters Values available ETS text...
Page 29
Thermostat Communication objects and ETS parameters Temperature Protection (A/B) This function is used to limit the temperature of the area controlled by the thermostat Temperature Protection Parameters Temperature Protection (A/B) With the "Temperature Channel" parameter you select the temperature to be monitored; when, in heating, it exceeds the value selected with the "Temperature Limit"...
Thermostat Communication objects and ETS parameters Relay The output can be configured as a normal switch or for the fan, with speed V1. Relay parameters Values available ETS text Comment [ Default value ] 0 = General Use 1 = Channel A: Fan coil For general use or control of Speed V1 solenoid valve from radiator...
Page 31
(both recep- and a COOLING valve), (38 if there is a proportional fan coil), tion and transmission). This function is dedicated to Vimar 39, 40, 41, 42, 43, (44 if there is a PROPORTIONAL fan), supervision software.
Page 32
Thermostat The KNX system uses the 1-byte object "Thermostat Mode" for the rising edge (closing of the window and contact). If to read the status of the thermostat. If you do not want to the contact is an N.O. type, the two parameters must be set use the Byte, you can set the 1-bit mode change object to respectively to "On"...
Page 33
YOU have to set to "Read" the relevant flags of objects from 25 to 32 and from 72 to 79 for each 02952 thermostat. 17. What is the parameter "Time in Manual Fan Mode" used for? It is a time indicated in the parameters for which the ther- mostat remains in "Manual forcing"...
Page 34
It enables the thermostat mode to be altered by acting on A 4, 5 and 6 are those of the 3 speeds and objects 46, 47, and B. On thermostats 02952 the "Enable Menu" parameter 48 for the thermostat and they can be controlled from the is enabled by default.
Page 35
Bus with operate. The season change is performed via bus by means messages. of communication object no. 66 for thermostat 02952 of “thermostat-B”. 35. Is it possible to operate a thermostat in such a way that in the summer it controls a 0-100% proportional valve Note.
Page 36
4-output module? The firmware version of the thermostat can be identified via the tracking label both on the VIMAR packing box and on the Yes, it is possible. The thermostat automatically performs body of the thermostat. The tracking label is similar to the...
Page 37
34 of the thermostat, so the fan coil will not air-conditioning circuit. switch on). 53. What is the difference between firmware version 2.00 49. Is it possible to have the thermostat 02952 send a 1 and 2.01? bit ON message when the thermostat turns off all the speeds? Firmware version 2.01 features improved neutral zone func-...