Vimar 02952 Installer Manual

Vimar 02952 Installer Manual

Knx touch thermostat.

Advertisement

Installer manual
02952
KNX touch thermostat.
BUILDING AUTOMATION

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 02952 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Vimar 02952

  • Page 1 Installer manual 02952 KNX touch thermostat. BUILDING AUTOMATION...
  • Page 2 Index...
  • Page 3 GENERAL CHARACTERISTICS AND FUNCTIONS from page 5 COMMUNICATION OBJECTS AND ETS PARAMETERS from page 7 from page 31...
  • Page 4 For all the details about the Well-contact Plus system, refer to the installer manual that can be downloaded from the Software  Product Software  Well-contact Plus section of the website: www.vimar.com.
  • Page 5 Fan coil Ambient Setpoint decrease speed humidity button 02952 Heating with boost function General characteristics The thermostat is suitable for controlling room temperature Air-conditioning with boost function (heating/air-conditioning) in 2 or 4 pipe systems (heating/air- conditioning) and neutral zone (only in 4-pipe systems), with Temperature display and thermostat B menu the "boost"...
  • Page 6 Thermostat General characteristics and functions Neutral zone The KNX 02952 thermostat is configured in Neutral Zone mode if the following object is NOT connected: "Enable A: Summer - The "Neutral Zone" is an operating mode of the thermostat (only Winter – control" or "Enable B: Summer - Winter – control".
  • Page 7 Thermostat Communication objects and ETS parameters List of existing communication objects and standard settings Flag 1 ETS name Function Description Type Priority C R W T U To see the temperature read by the thermostat sensor (to see the temperatures measured by thermostats A/B Internal sensor Internal probe temperature 2 byte...
  • Page 8 Thermostat Communication objects and ETS parameters Continued Flag 1 ETS name Function Description Type Priority C R W T U To read the seasonal mode set on the thermostat (0 = Status A: Summer - Winter - status 1 bit - Low Summer, 1 = Winter) To set the seasonal mode on the thermostat (1 = Win-...
  • Page 9 Thermostat Communication objects and ETS parameters Continued Flag 1 ETS name Function Description Type Priority C R W T U If the "Valve" parameter is set for 4-pipe proportional systems for Winter valve management: to be used to Heating Valve A: Valve 1 byte - Low...
  • Page 10 Thermostat Communication objects and ETS parameters Continued Flag 1 ETS name Function Description Type Priority C R W T U Thermostat A: Scenario Scenario A: Scenario To activate a scenario with a 1 Byte message 1 byte - W - - Low Thermostat A: Auto/Man Temperature: Automat-...
  • Page 11 Thermostat Communication objects and ETS parameters Continued Flag 1 ETS name Function Description Type Priority C R W T U Winter Comfort B: Setpoint - status, control To read and set the Winter Comfort setpoint. 2 byte R W T U - Low Winter Standby B: Setpoint - status, control...
  • Page 12 Thermostat Communication objects and ETS parameters Continued Flag 1 ETS name Function Description Type Priority C R W T U Used to force activation of fan coil speed V2 (if the V2 speed B: Fan Inputs 1 bit - W - - Low selected fan has 3 speeds) Used to force activation of fan coil speed V3 (if the...
  • Page 13 Thermostat Communication objects and ETS parameters Continued Flag 1 ETS name Function Description Type Priority C R W T U NOT USED Used for viewing, on the thermostat display, the trigger- General Alarm 1 bit C R - ing of a generic alarm on the KONNEX BUS Input Input Device IN control...
  • Page 14: General Parameters

    Visibility of operating bling the operating modes mode setting button on the display CAUTION: If you use thermostats art. 02952 with firmware [ Yes ] version 1.00 do not use the setting: Percentage displayed = Humidity. Possibility of disa- Heating icon visible...
  • Page 15 Thermostat Communication objects and ETS parameters Value Enable Menu=Enable Enable Menu=Enable Enable Menu=Disable Displayed Button Activation = Enable Button Activation = Disable Button Activation = Enable Display Current Temperature Setpoint Current Display Off View Difference Setpoint Note: In "View Setpoint Difference" mode, the difference between the Setpoint set via configuration by ETS and the Setpoint modified locally by the user is displayed.
  • Page 16 Thermostat Communication objects and ETS parameters Backlighting Backlighting Parameters Backlighting Off Values available ETS text Comment [ Default value ] 0 = Off Always off On when pressing the touch Ecometer Mode buttons. 1 = ON push button Note: after some time of Backlighting inactivity, the backlighting turns off.
  • Page 17: Sensor Parameters

    Values available ETS text Comment [ Default value ] For the thermostat's internal 0... 100 sensor, the Vimar wired NTC probe (if present) and the KNX Temperature sen- probes, this determines the sor weightings relative importance for calcu- [ 0 ]...
  • Page 18: Setpoint Parameters

    Thermostat Communication objects and ETS parameters Setpoint (A/B) Setpoint parameters Values available ETS text Comment [ Default value ] 1 = Comfort 2 = Standby 3 = Energy saving Mode at bus power Thermostat operating mode at bus power on 4 = Protect 255 = Last Mode Selected...
  • Page 19: Setpoint Range

    Thermostat Communication objects and ETS parameters Temperature Setpoint (A/B) Sensor parameters Continued Values available Values available ETS text Comment ETS text Comment [ Default value ] [ Default value ] Winter Comfort Setpoint See "Range" table [20] If you set "On" you can set the Winter Standby Setpoint [18]...
  • Page 20: Control Parameters

    Thermostat Communication objects and ETS parameters Window sensor (A/B) Sensor parameters Values available ETS text Comment [ Default value ] 0 = Off Sets the time delay that Window sensor heating/air conditioning 8 = 120 sec. delay stops after window open detection [ 4 = 30 ] Window sensor (A/B)
  • Page 21: Proportional/Integral (Pi) Control

    Thermostat Communication objects and ETS parameters Proportional/Integral (PI) control Continuous integral proportional: PI control with proportional valve This type of control uses a more advanced algorithm that keeps the temperature inside the room more stable, increasing comfort. This algorithm works by switching the system on and off so as to be like a gradual increase or decrease in the system's thermal (or refrigerating) power.
  • Page 22 Thermostat Communication objects and ETS parameters Continued Values available ETS text Comment [ Default value ] 5 min. 6 min. 7 min. Integral band (A/B) 8 min. 9 min. 10 min. 12 min. 15 min. 17 min. Integral Cooling Value 20 min.
  • Page 23 Thermostat Communication objects and ETS parameters Valve (A/B) Valve parameters Values available ETS text Comment [ Default value ] 0 = 2-Pipe Circuit On/ 2-Pipe Circuit On/Off (A/B) 1 = 4-Pipe Circuit On/ Select according to the type System Layout of installed system 2 = 2-Pipe Proportional 3 = 4-Pipe Proportional...
  • Page 24 Thermostat Communication objects and ETS parameters Heating/Cooling Stage (A/B) "Boost" The second stage is used to control a second heating or cooling source that allows the "boost" function. The "boost" function enables the second auxiliary source when the Stage Disabled (A/B) current temperature differs from the current setpoint by more than the set threshold.
  • Page 25: Fan Parameters

    Thermostat Communication objects and ETS parameters Fan (A/B) Fan parameters Continued Values available Values available ETS text Comment ETS text Comment [ Default value ] [ Default value ] No thermostat controlled fan coil. Disables the graphics for Duration of "Manual Forcing" 0 = Off the fan on the thermostat for the fan speed if the guest...
  • Page 26 Thermostat Communication objects and ETS parameters Manual operation of the fans The user selects the speed used by the thermostat only when the valve is on; if the valve is off at the time of selection, the thermostat saves the setting and uses it again the next time the valve is on.
  • Page 27 Thermostat Communication objects and ETS parameters Proportional fan coil operation Proportional fan operation is similar to that of the three-speed fan coil. When the valve is OFF the proportional speed is equal to 0%; when the valve is ON the value of the proportional speed depends on the difference between the setpoint and the temperature measured in the room.
  • Page 28 Thermostat Communication objects and ETS parameters Scenario (A/B) 16 scenarios are available. 16 different scenarios can therefore be saved on the device output. With Enable Scenario Learning you can also set the status of the output for the desired scenario with a message from the bus (scene learn). Scenario parameters Values available ETS text...
  • Page 29 Thermostat Communication objects and ETS parameters Temperature Protection (A/B) This function is used to limit the temperature of the area controlled by the thermostat Temperature Protection Parameters Temperature Protection (A/B) With the "Temperature Channel" parameter you select the temperature to be monitored; when, in heating, it exceeds the value selected with the "Temperature Limit"...
  • Page 30: Relay Parameters

    Thermostat Communication objects and ETS parameters Relay The output can be configured as a normal switch or for the fan, with speed V1. Relay parameters Values available ETS text Comment [ Default value ] 0 = General Use 1 = Channel A: Fan coil For general use or control of Speed V1 solenoid valve from radiator...
  • Page 31 (both recep- and a COOLING valve), (38 if there is a proportional fan coil), tion and transmission). This function is dedicated to Vimar 39, 40, 41, 42, 43, (44 if there is a PROPORTIONAL fan), supervision software.
  • Page 32 Thermostat The KNX system uses the 1-byte object "Thermostat Mode" for the rising edge (closing of the window and contact). If to read the status of the thermostat. If you do not want to the contact is an N.O. type, the two parameters must be set use the Byte, you can set the 1-bit mode change object to respectively to "On"...
  • Page 33 YOU have to set to "Read" the relevant flags of objects from 25 to 32 and from 72 to 79 for each 02952 thermostat. 17. What is the parameter "Time in Manual Fan Mode" used for? It is a time indicated in the parameters for which the ther- mostat remains in "Manual forcing"...
  • Page 34 It enables the thermostat mode to be altered by acting on A 4, 5 and 6 are those of the 3 speeds and objects 46, 47, and B. On thermostats 02952 the "Enable Menu" parameter 48 for the thermostat and they can be controlled from the is enabled by default.
  • Page 35 Bus with operate. The season change is performed via bus by means messages. of communication object no. 66 for thermostat 02952 of “thermostat-B”. 35. Is it possible to operate a thermostat in such a way that in the summer it controls a 0-100% proportional valve Note.
  • Page 36 4-output module? The firmware version of the thermostat can be identified via the tracking label both on the VIMAR packing box and on the Yes, it is possible. The thermostat automatically performs body of the thermostat. The tracking label is similar to the...
  • Page 37 34 of the thermostat, so the fan coil will not air-conditioning circuit. switch on). 53. What is the difference between firmware version 2.00 49. Is it possible to have the thermostat 02952 send a 1 and 2.01? bit ON message when the thermostat turns off all the speeds? Firmware version 2.01 features improved neutral zone func-...
  • Page 38 Viale Vicenza 14 36063 Marostica VI - Italy www.vimar.com 02952IEN 01 2010...