Setup
Programming OFF TIME Duration
After setting the parameters for either Pressure (Pr),
Cycle (CY) or Time (Ti) ON Modes, the OFF TIME or
PUMP REST CYCLE must be set up.
The LED below the OFF TIME Symbol Illu-
minates.
NOTE: The HH field is a 2-digit number.
Enter a leading zero (0) in the first field if
the number of hours is fewer than 10. The
highest number that can be set for the HH
field value is 99.
To set the OFF Time:
1. Use the UP or DOWN arrow
button to scroll through the
numerals 0 to 9 until the desired
number appears in the first Hours
(HH) field. 
2. Press ENTER.
The next HH number field to the right
flashes, indicating it is ready for programming.
3. Use the UP or DOWN arrow button to scroll through
the numerals 0 to 9 until the desired number
appears in the second HH field.
4. Press the ENTER button.
The next number field to the right flashes indicating it is
ready to program the Minutes (MM) fields.
NOTE: The MM field is a 2-digit number. Enter a leading
zero (0) in the first field if the number of minutes is fewer
than 10. The highest number that can be set for the MM
field value is 59.
5. Repeat steps 1 to 4 to set the MM fields.
6. Press the ENTER button to lock in the last MM field.
The controller automatically switches to the LOW
LEVEL SETUP MODE.
16
Programming the Low Level Setting
NOTE: If Low Level is not used (i.e., low level inputs are
not connected), configuring the low level setting is still
required. The unit's default settings (LL:01) can be used.
1. Use the UP or DOWN arrow
button to select the low level
setting.
2. Press ENTER.
LL:01 - Default
This is the default low level setup when
working with a standard, normally open,
low level switch. The pump stops when
the low level occurs.
The unit enters a low level fault condition after the
switch input is closed for more than 1 second when the
unit is in the ON portion of the RUN MODE.
When low level occurs:
The pump stops
The unit displays ER:LL
A buzzer sounds
The alarm LED illuminates
The alarm output contact is closed
To Clear Alarm Buzzer
Press RESET button to silence the
buzzer.
To Clear Low Level Alarm
Resolve low level condition at low level sensor (i.e., fill
the reservoir).
Press and hold RESET button for
three (3) seconds.
3A2960G