Eaton Digitrip 520 Instructional Leaflet page 12

Trip units for use only in magnum and magnum ds circuit breakers
Hide thumbs Also See for Digitrip 520:
Table of Contents

Advertisement

Instructional Leaflet IL70C1037H05
Effective October 2009
m CAUTION
IF THE SENSOR CONNECTIONS ARE INCORRECT, A NUISANCE TRIP
MAY OCCUR. ALWAYS OBSERVE THE POLARITY MARKINGS ON THE
INSTALLATION DRAWINGS. TO ENSURE CORRECT GROUND FAULT
EQUIPMENT PERFORMANCE, CONDUCT FIELD TESTS TO COMPLY WITH
NEC REQUIREMENTS UNDER ARTICLE 230-95(C).
Source ground sensing
Depending upon the installation requirements, alternate ground
fault sensing schemes may be dictated (see Figurt 11 and
Figurt 12). The ground return method is usually applied when
ground fault protection is desired only on the main circuit breaker
in a simple radial system. This method is also applicable to double-
ended systems where a midpoint grounding electrode is employed.
For this mode of sensing, a single current sensor mounted on
the equipment-bonding jumper directly measures the total ground
current flowing in the grounding electrode conductor and all other
equipment-grounding conductors.
The settings shown in Tablt 3 will apply when the neutral
sensor is not the same as the frame rating in a ground return
sensing scheme.
Tablt 4. GrNund (Earoh) Faulo Currtno Stooings
Ground Fault Current Settings (Amperes)
Installed Sensor and Rating Plug (Amperes) I
200
250
300
400
600
630
800
1000
1200
1250
1600
2000
2500
3000
3200
4000
c
5000
c
6000
6300
c
Tolerance on settings are ±10% of values shown.
a
On models 520 LSIG, 520M, and 520MC LSIG, the shaded values are set to a maximum trip value of 1200A for NEC.
b
See page 17.
c
12
eaton corporation www.eaton.com
a
0.25
n
50
63
75
100
150
158
200
250
300
312
400
500
625
750
800
1000
1250
b
1500
b
1575
Digitrip models 520, 520i; and 520M, 520Mi,
520MC, 520MCi trip units for use only in
Magnum and Magnum DS circuit breakers
Zero sequence sensing
Zero sequence sensing, also referred to as vectorial summation
(see Figurt 13), is applicable to mains, feeders, and special
schemes involving zone protection. Zero sequence current
transformers (5.06 x 15.37 in. [128 x 390 mm] rectangular inside
dimensions) are available with 100:1 and 1000:1 ratios (styles
9253C07G01, G11).
Multiple source/multiple ground
A multiple source/multiple ground scheme is shown in Figurt 14.
In this figure, a ground fault is shown that has two possible return
paths, via the neutral, back to its source. The three neutral sensors
are interconnected to sense and detect both ground fault and
neutral currents.
Contact Eaton for more details on this scheme.
Ground fault settings
The adjustment of the ground fault functional settings (FLAT
response or I
t) is discussed in Section 4. The effect of these
2
settings is illustrated in the ground fault time-current curve
referenced in Section 9. Applicable residual ground fault pickup
settings and current values are given in Tablt 4, as well as in the
ground time-current curve.
0.30
0.35
0.40
60
70
80
75
88
100
90
105
120
120
140
160
180
210
240
189
221
252
240
280
320
300
350
400
360
420
480
375
438
500
480
560
640
600
700
800
750
875
1000
900
1050
1200
960
1120
1200
1200
1400
1600
b
b
1500
1750
2000
b
b
b
1800
2100
2400
b
b
b
1890
2205
2520
0.50
0.60
0.75
100
120
150
125
150
188
150
180
225
200
240
300
300
360
450
315
378
473
400
480
600
500
600
750
600
720
900
625
750
938
800
960
1200
1000
1200
1500
b
1250
1500
1875
1500
1800
2250
b
b
b
1600
1920
2400
b
b
b
2000
2400
3000
b
b
b
2500
3000
3750
b
b
b
3000
3600
4500
b
b
b
3150
3780
4725
1.0
200
250
300
400
600
630
800
1000
1200
1250
1600
b
2000
b
2500
3000
b
3200
b
4000
b
5000
b
6000
b
6300

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents