9 Available protection settings
bit
mask
set point
Register
field
field
name
403004
Style1
403005
3-0
0x000F Style2
403006
0
0x0001 LD thermal
memory
403007
0
0x0001 ZSI
403008
0-1
0x0003 LD_slp
403009
LD pick up (Ir)
403010
LD time (tr)
403011
High load
alarm
403012
0
0x0001 SD slp
403013
SD pick up
(Isd)
403014
SD time (tsd)
403015
Instantaneous
pick up(Ii)
403016
0
0x0001 Ground
sensing type
403017
0-1
0x0003 Local ground
fault type
403018
0
0x0001 Ground fault
slope
403019
Ground pick
up(Ig)
42
PXR tRiP units foR PoweR Defense molDeD case ciRcuit bReakeRs MN012007EN June 2018 www.eaton.com
R/w
format
Value definition
R
Encoded
b0 --> LdSel : with long delay protection
0 = false
b1 --> SdSel : with short delay protection
1 = true
b2 --> InstSel : with Inst protection
b3 --> GfSel : with ground fault protection
b4 --> ARMSel : with maintenance mode
b5 --> OvrideSel : with override protection
b6 --> RCDSel : with ground fault RCD
b7 --> MotorSel : with motor protection
b8 --> NeuSenorSel : with neutral sensor
b9 --> ThermalSel : with thermal memory
b12 --> VoltSel : with voltage sampling feature
b13 --> ExtADCSel : with external AD7779
R
Encoded
b0 --> ModbusSel : with integrated Modbus
0 = false
b1 --> CAMSel : with CAM RS422 port
1 = true
b2 --> IOModuleSel : with IO module port
b3 --> RelaySel : with relay
b4 --> ZSISel : with ZSI
b12 --> NZM_ACB_Sel
b13 --> ECSel : IEC = 1, UL = 0
R/W Encoded
thermal memory enable/disable
LD Thermal Memory (powered and unpowered
operation. Used only in I
trip unit :
0 <--> off
1 <--> cooling
R/W Encoded
ZSI, zone interlock
*when enable, for trip unit with G, ZSI is
implemented for short delay and ground fault.
*when enable, for trip unit without G, ZSI is
implemented for short delay.
trip unit side :
0 <--> disable
1 <--> enable
R/W Encoded
long delay slope:
0 = I
T
0.5
2 = I
T
2
R/W Unsigned long delay pick up:
detail see the "PXR MCCB amp rating labels"
Ir = xxx ( A )
R/W Unsigned long delay time:
detail see the "PXR MCCB amp rating labels"
Tr = xxx /10 ( s )
R/W Unsigned high load alarm level [100... 110] step 1
100%Ir...110%Ir
R/W Encoded
Short delay slope:
0 = flat
R/W Unsigned Short delay pick up:
detail see the "PXR MCCB amp rating labels"
Isd = xxx /10 ( xIr )
R/W Unsigned long delay time:
detail see the "PXR MCCB amp rating labels"
Tsd = xxx / 1000 ( s )
R/W Unsigned Instantaneous pick up:
detail see the "PXR MCCB amp rating labels"
Ii = xxx /10 ( xIn )
R
Encoded
Ground sensing type setting:
MCCB only support residual mode
0 = residual
1 = source/zero sequence
R/W Encoded
Ground fault style - trip/alarm/OFF
0 = Trip
2 = OFF
R/W Encoded
Ground fault slope:
0 = Flat
R/W Unsigned Ground fault pick up:
detail see the "PXR MCCB Amp Rating Labels"
Ig = xxx / 100 ( x In )
t and I
t)
2
4
1 = IT
3 = I
T
4
1 = I
T
2
1 = Alarm
1 = I
T
2
unit
A
Sec
%
*Ir
ms
*In
*In