1.2 Metering features

The following table shows the electrical system information which is metered by the trip
unit. It is available for viewing in PXPM, on the display (if equipped) or for reading via
communication channels.
metering data
Current
Current maximum and minimum
Voltage line to line and line to neutral
Voltage maximum and minimum ( L-L and L-N )
Power kW (real, demand, peak)
Power kVAR (reactive, demand, peak)
Power kVA (apparent, demand, peak)
Energy kWh (total, fwd, rev) VARh (net), VAh (net)
Frequency
Power factor
1.2.1 Metered data specifications
Metered data accuracy is as follows:
metered value
Range of conditions (units)
5 to 10 % of In (A)
Current (I)
10 to 120 % of In (A)
60 to 102 (V)
Voltage (V)
102 to 690 (V)
690 to 750 (V)
5% to 10% of In (A)
102 to 690 (V)
Power factor = 1
Power (kW)
Energy (kWh)
10 to 120 % of In (A)
102 to 690 V
Power factor = 1
10 to 20 % of In (A)
102 to 690 (V)
PF = 0.5 inductive or 0.8 capacitive
Power (kW)
Energy (kWh)
20 to 120 % of In (A)
102 to 690 (V)
PF = 0.5 inductive or 0.8 capacitive
Note:
Accuracy is expressed as % of reading, currents are RMS, voltages are line-to-line.
PXR tRiP units foR PoweR Defense molDeD case ciRcuit bReakeRs MN012007EN June 2018 www.eaton.com
1. Introduction to the Power Xpert® Release trip unit
PXR 10
PXR 20
*
*
*
PXR 10
PXR 20
5.0 %
5.0 %
5.0 %
2.0 %
not applicable
PXR 20D
PXR 25
*
*
*
*
*
*
*
*
*
*
*
*
PXR 20D
PXR 25
1.0 %
1.0 %
0.5 %
0.5 %
1.0 %
0.5 %
1.0 %
1.5 %
1.0 %
1.5 %
1.0 %