6 Power Xpert® Protection Manager - configuration software
Typical actions available from the configuration screens include:
View and edit set points - For each set point, its range, step size and description are
•
shown in the tooltip when a user hovers the mouse cursor over that set point. A blank
space for a set point indicates that user may work in offline mode, and cannot edit the
read-only set point.
Change trip unit - Takes user back to "Create New Offline Setting Screen" to modify trip
•
unit's settings.
Save (visible in open settings) - Saves changes in set points. Note that if set points have
•
already been saved to a file, click save button will overwrite the file with new set points.
Save as - Saves set points to a configuration file. Users will be prompted to select a loca-
•
tion and a name for the configuration file.
Export - Sends the set points to a trip unit. The trip unit must be connected to the
•
computer through a USB to Micro-USB cable for successful operation.
18
PXR tRiP units foR PoweR Defense molDeD case ciRcuit bReakeRs MN012007EN June 2018 www.eaton.com