Eaton Power Xpert Release PXR 10 Manual page 48

Units for power defense molded case circuit breakers
Hide thumbs Also See for Power Xpert Release PXR 10:
Table of Contents

Advertisement

9 Available protection settings
bit
mask
Register
field
field
set points name
403008
INCOM CAM baud rate
403009
Ethernet CAM DHCP enable
403010
Ethernet CAM IP addr. MSB
403011
Ethernet CAM IP addr. LSB
403012
Ethernet CAM IP addr. MSB
403013
Ethernet CAM IP addr. LSB
403014
Ethernet CAM subnet mask
403015
Ethernet CAM default gateway
403016
Ethernet CAM default gateway
403017
Ethernet CAM reset pin
403018
Profibus CAM address
Set points group 4: I/O module group
bit
mask
Register
field
field
set points name
403000
15-0
0xFFFF
Password
403001
15-0
0xFFFF
I/O module cfg
403002
15-0
Validity flags 0....15
403003
15-0
Validity flags 16....31
403004
15-0
0: digital output 0
403005
15-0
1: digital output 1
403006
2: digital output 2
403007
3: digital output 3
403008
4: S0 channel 0 type
403009
5: S0 channel 0 scale
403010
6: S0 channel 0 pulse
403011
7: S0 channel 1 type
403012
8: S0 channel 1 scale
403013
9: S0 channel 1 pulse
403014
10: Modbus address
44
PXR tRiP units foR PoweR Defense molDeD case ciRcuit bReakeRs MN012007EN June 2018 www.eaton.com
R/w
format
Value definition
R
1 <--> 9600bps see IL01301033e
P8 "for series NRX INCOM
communication adapter module,
baud rate is fixed at 9600 baud and
represented by a value of 01"
R
0 <--> false
1 <--> true
R
0~255 <--> 0~255
R
0~255 <--> 0~255
R
0~255 <--> 0~255
R
0~255 <--> 0~255
R
16~32 <--> 16~32
R
0~255 <--> 0~255
R
0~255 <--> 0~255
R
0~255 <--> 0~255
R
1~125 <--> 1~125
R/w
format
Value definition
W
Encoded Default "0000"
R/W Encoded 0x04FF
R/W Encoded For each bit:
0 : corresponding parameter inactive
1 : corresponding parameter active
e.g. Bit 8 = 1
==> parameter 8 = active
R/W Encoded For each bit:
0 : corresponding parameter inactive
1 : corresponding parameter active
e.g. Bit 8 = 1
==> parameter 8 = active
R/W Encoded
R/W Encoded
R/W Encoded
R/W Encoded
R/W
0: output disabled
1: sends pulses based on active energy
2: sends pulses based on reactive energy
3: sends pulses based on apparent energy
R/W
0: sends a pulse every
1: W 1: sends a pulse every 10 W
2: sends a pulse every 100 W
3: sends a pulse every 1000 W
R/W
pulse duration x *10 ms
range: 1...50 ==> 10...500 ms
R/W
0: output disabled
1: sends pulses based on active energy
2: sends pulses based on reactive energy
3: sends pulses based on apparent energy
R/W
0: sends a pulse every
1 W 1: sends a pulse every 10 W
2: sends a pulse every 100 W
3: sends a pulse every 1000 W
R/W
Pulse duration x *10 ms
Range: 1...50 ==> 10...500 ms
R/W
Modbus ID (= device address)
permitted range: 1...255