Eaton Power Xpert Release PXR 10 Manual page 51

Units for power defense molded case circuit breakers
Hide thumbs Also See for Power Xpert Release PXR 10:
Table of Contents

Advertisement

Register
format
408232
Unsigned16
408233
Unsigned16
408234
Unsigned16
408235
Signed32
408237
Signed32
408239
Unsigned32
408241
Signed32
408243
Signed32
408245
Unsigned32
408247
Singed16
408248
Unsigned16
408249
Singed16
408250
Unsigned16
408251
B31-b00
Historical alarm
Register
format
408193
Encoded
408194
Unsigned32
408196
Unsigned32
408198
Unsigned32
408200
Unsigned32
408202
Unsigned32
408204
Date/time
408212
Encoded
408213
B0
408214
Encoded
Note: address 408225 and 408227 are both ground current. According to the set point 'Ground Sensing' setting in set
points group 1: protection group, the actual ground current would be displayed in related register and value in the other
register would be zero. For example, if the 'Ground Sensing' setting is 0, representing the ground current sensing type is
residual ground current. IG residual in address 408227 would be the actual value and IG source in address 408225 would
be zero.
10.3.5 Block of registers
A block of registers can be established in trip unit to remap the data object registers of an
Eaton product. The block of registers is stored in non-volatile memory.
Function code 16 is used to load the object assignments for the block of registers. The block
assignments are stored beginning at 401001/420481 (0x03E8/0x5000). Only the first data
object register address is assigned within the block of registers. For example, although data
object IA occupies register 0x1202 and 0x1203, only register 0x1202 is loaded into the block
of assignment registers. Verification of this block of assignment registers can be read from
trip unit with a function code 03 or 04 from these 401001/420481 (0x03E8/0x5000) registers.
Data pertaining to the objects configured in the block of assignment registers is mapped into
registers starting at 401201/420737 (0x 04B0/0x5100) and continuing in successive order for
each object assigned. The number of objects and their placement order in this data block of
registers is dependent on the configuration of the block of assignment registers. The total
number of data block of registers is limited to 100.
The data can be obtained from the data block of registers by a read function code 03 or
04. The address of the starting object must be aligned with a starting address of an object
within the data block of registers. The number of registers to obtain must align with an
ending address of an object within the data block of registers.
PXR tRiP units foR PoweR Defense molDeD case ciRcuit bReakeRs MN012007EN June 2018 www.eaton.com
R/w
Descriptions
R
VAN
R
VBN
R
VCN
R
Real 3 phase power
R
Reactive 3 phase power
R
Apparent 3 phase power
R
Real 3 phase power demand
R
Reactive 3 phase power demand
R
Apparent 3 phase power demand
R
Device temperature
R
Frequency
R
Apparent power factor
R
Operations count
R
Binary status with validity bits
R/w
Historical summary event
R/W
Event type: summary = 81FF
R
Earliest event ID
R
Latest event ID
R/W
Requested event ID
R
Previous event ID
R
Next event ID
R
Date/time
R
Format of data: minor alarm = 0006
R
Object validity bit
R
Status cause(primary, secondary, cause)
9 Available protection settings
units
V
V
V
W
VAR
VA
W
VAR
VA
1/10 °C
1/10 Hz
1/100 pf
16
16
47