10.3.3 Set points registers
The trip unit's set points are organized into groups. Each group can be considered as a
binary array of information which can be obtained through Modbus register access. Register
403001 is an R/W register used to select the particular group (Default selected group 0).
The high byte contains the requested group number, while the low byte must contain
255(0FF16). The set points register can be read using function code 03 or 04. Register
403001 can be written using function code 06 or 16. For trip units which support write set
points capabilities, the set points group 0/1/2 should be written one by one using function
code 06, the set points group four should be written the whole group using function code
16. Before reading or writing the set points, register 403001 should be written to choose
corresponding group. Before writing any set points, you must input correct password, and
write the set points within ten seconds after password checks ok.
Set points group 0: system group
Register
bit
mask
set point
number
field
field
name
403000
15-0
Password
403001
15-0
0xFFFF Group 0 = system R/W
403002
12-0
0x1FFF
Rating
information
403003
2-0
0x0007 Breaker frame
PXR tRiP units foR PoweR Defense molDeD case ciRcuit bReakeRs MN012007EN June 2018 www.eaton.com
R/w
format
Value definition
W
"0000" (factory default)
0x00FF
R
Encoded
PD2
PD3A: 125, 250, 400.
PD3B: 400, 600, 630.
PD4: 800, 1000.
PD5:
PD6:
R
Encoded
00 --> NRX NF
01 --> NRX RF
11 --> NZM2
12 --> NZM3
13 --> NZM4
21 --> PD2
22 --> PD3-A
23 --> PD3-B
24 --> PD4
25 --> PD5
26 --> PD6