Changing The Lamp; Maintenance Test - dehn PHEG1 FD Series Instructions For Use Manual

Voltage detectors
Hide thumbs Also See for PHEG1 FD Series:
Table of Contents

Advertisement

Available languages

Available languages

6.2
Changing the lamp (see Fig. 6)
Remove the cover as described in 6.1
Both lamps 7, 8 are now accessible and can be unscrewed. Only replace them with lamps of the
same type (mini bulb GL 3.5 V 0.2 A E10).
Re-assemble in reverse order (sealings for screws and cover may not be removed).
Perform a functional test according to 5.1.
7/ 8
6
Fig. 6
7.

Maintenance test

The test interval for a PHEG... voltage detector depends on its conditions of use, for example
frequency of use, environmental conditions and transport.
According to DGUV regulation 3 (formerly BGV A3), the voltage detectors should undergo a
maintenance test at least every 6 years.
The next maintenance test is documented on the device
5
1/2
2024
1
2
3
4
3/4
11