Using The Voltage Detector In An Installation - dehn PHEG1 FD Series Instructions For Use Manual

Voltage detectors
Hide thumbs Also See for PHEG1 FD Series:
Table of Contents

Advertisement

Available languages

Available languages

lamp " " "Test" button Lamp "0"
functional test
Indication
Permanent green light
Flashing red light
No light
Green and red lights flash simultaneously
Fig. 5.1 Functional test
5.2

Using the voltage detector in an installation

After performing a functional test, the green light "0" illuminates indicating that the device is
ready for testing.
Note:
If PHEG1... voltage detectors are used, always connect the earth clamp before the test electrode.
Disassembly in reverse order.
Please note that voltage tests may only be performed when the green lamp "0" is lit up,
indicating that the voltage detector is ready for testing.
The status "ready for testing" applies for as long as the voltage detector is ready for operation.
After that, the device switches itself off automatically. If further tests are to be carried out, press
the "TEST" button again to perform a functional test.
The voltage detector is immediately ready for testing again. If "voltage present" is indicated, an
electronic lock prevents the device from automatically switching off during testing. After testing,
the device remains ready for testing (green light "0" is illuminated) for the period in which it
remains ready for operation.
Another functional test must be performed after testing.
lamp " " "Test" button Lamp "0"
0
ready for testing
Voltage/operating state
No voltage present
Voltage present
Functional test not performed
(see 5.1)
Low battery (replace battery)
lamp " " "Test" button Lamp "0"
0
battery replacement
9