Transmitter Installation; Supply Voltage; Figure 4-1: Maximum Loop Resistance (Ω); Table 4-1: Maximum Loop Resistance (Ω) - Honeywell SmartLine SLN 700 Series User Manual

Level transmitter, non-contact radar
Hide thumbs Also See for SmartLine SLN 700 Series:
Table of Contents

Advertisement

4.1

Supply voltage

(4-20) mA / HART (2-Wire
Power supply and the output current signal are carried by the same two-core cable. The allowed
supply voltage range is 12V to 30Vdepending on loop resistance. There must always be
between 12V and 30V on the transmitter terminals, regardless of loop current. A safety barrier
(refer to
Table 3-1
instrument for the intrinsically safe version.
The grounding mode of current output can be adopted for the standard instrument, while the
floating current output should be adopted for the intrinsically safe instrument. Normally, the
grounding terminals can be connected to the grounding point of tank or an available nearby
ground in case of plastic tank.
Maximum Loop Resistance (Ω)
Revision 1
4

Transmitter Installation

)
for detailed specification) must be placed between the power supply and
Maximum Loop Resistance (Ω)
:
Figure 4-1
Table 4-1: Maximum Loop Resistance (Ω)
Supply
Voltage (VDC)
12
17.5
23
30
SLN 700 SmartLine NCR Level Transmitter User's Manual
Max. Loop
Resistance (Ω)
0
250
500
818
Page 13