4.9 Damp
Time
4.10 Max
Level Speed
4.11 First
Echo
Revision 1
When the LCD menu number is
time setting menu. Display in LCD is as follows.
Damp time
To damp process-dependent measured value fluctuations, set an
integration time of 1 ... 20 s in this menu item. Default setting is 8.
Press
to enter the status of parameter editing. Use the key to set
the number and the key to select the edit digit. Press
after the editing is completed.
Max Level Speed
Define Maximum rate of filling or emptying. Default setting is 0.2m/s.
When selecting liquid or solid material properties, and when the LCD
menu is
4.10, use
echo menu. Display in LCD is as follows.
First Echo
Press
First Echo
Biggest
Normal
Small
This (Engineering) parameter is used set probability of assigning the first
echo as the correct reflection. When set to 'Biggest' the first signal above
threshold is selected regardless of whether the echo curve contains other,
larger reflections. Default is Normal. This parameter should only be
modified in unique applications where false echo suppression is not an
option.
SLN 700 SmartLine NCR Level Transmitter User's Manual
4.9, press
key to select the next menu to enter the first
to enter the first echo menu. Display in LCD is as follows.
Big
Bigger
key to enter the damp
to confirm
Page 29