3RA61/3RA62 compact starter
5.5 Installing/removal
5.5.2.3

Removing the compact starter from an infeed system for 3RA6

Requirements
● Screwdriver with max. diameter of 7.5 mm and minimum shaft length of 100 mm for
releasing the compact starter
● The compact starter must be switched off (actuator set to
Procedure
For servicing purposes, the compact starter can be removed from the infeed system while
the system is live but at zero current.
Note
The fact that the SIRIUS infeed system for 3RA6 features permanent wiring means that
there is no need to disconnect the main circuit terminals.
Step
1
2
3
72
NOTICE
Compact starter and infeed system material damage!
You can damage the compact starter and the infeed system if you remove the compact
starter from the infeed system for 3RA6 while the starter is switched on (actuator in the
READY position).
Make sure that the compact starter's actuator is set to the
remove the compact starter from the infeed system for 3RA6.
Instructions
Insert a screwdriver into the opening.
Tilt the screwdriver to the right and then
down (see arrow on enclosure lid) so
that you can push the compact starter
forwards by approx. 5 mm.
Move the compact starter forwards to
remove it from the screw-type infeed or
extension block.
OFF position).
OFF position before you
Image
SIRIUS 3RA6 compact starter
System Manual, 08/2018, NEB560060102000/RS-AB/007