5.8
Diagnostics
5.8.1
Diagnostics via auxiliary and signaling contacts
Signaling contacts on the 3RA61 compact starter (direct starter)
Table 5- 13
Status of the signaling contacts on the 3RA61 compact starter (direct starter)
Compact starter status Actuator
Switched off (delivery
condition)
Control supply voltage
present with actuator
set to OFF
Ready
Switched on
Overload protection function
Overload tripped
Short-circuit protection function
Short circuit tripped
Malfunction (e.g. end of service life reached)
Malfunction tripped
SIRIUS 3RA6 compact starter
System Manual, 08/2018, NEB560060102000/RS-AB/007
Main contacts
OFF
Open
OFF
Open
READY Open
READY Closed
READY Open
TRIPPED
Open
TRIPPED Open
Auxiliary and signaling contacts
Auxiliary contacts
"Overload" signaling
contact
Querying the
position of the
main contacts
13/14: Open
95/96: Closed
95/98: Open
21/22: Closed
13/14: Open
95/96: Closed
95/98: Open
21/22: Closed
13/14: Open
95/96: Closed
95/98: Open
21/22: Closed
13/14: Closed
95/96: Closed
95/98: Open
21/22: Open
13/14: Open
95/96: Open
95/98: Closed
21/22: Closed
13/14: Open
95/96: Closed
95/98: Open
21/22: Closed
13/14: Open
95/96: Closed
95/98: Open
21/22: Closed
3RA61/3RA62 compact starter
5.8 Diagnostics
"Fault" signaling
contact
77/78: Open
—
—
77/78: Open
—
—
77/78: Closed
—
—
77/78: Closed
—
—
77/78: Closed
—
—
77/78: Open
—
—
77/78: Open
—
—
87