User Guide | Optyma™ control AK-RC 113 three phase
1.0 Introduction

1.1 General

2.0 Technical
Characteristics

2.1 Product ID Codes

2.2 Product Series –

Technical Characteristics

© Danfoss | DCS (vt) | 2020.03
The OPTYMA™ Control three-phase is a controller for refrigeration systems with a three-phase
compressor or for controlling the three-phase evaporating unit only, for complete cold room
management. Front access to the automatic fuse and motor protector for the compressor and an
innovative design combine to make it the ideal choice for effective refrigeration control.
Applications:
• Complete management of three-phase refrigerating systems up to 7.5 HP static or ventilated, with
off-cycle or electrical defrosting.
Line of electrical panel of OPTYMA
Identification codes
080Z3221
080Z3222
Line of electrical panel of OPTYMA
Identification codes
080Z3226
080Z3227
Technical characteristics
Box dimensions
Weight
Protection rating
Power supply (3F+N+T)
Load type
Operating temperature
Storage temperature
Relative ambient humidity
Altitude
Main switch / general protection
Interruption power
Compressor protection
Defrosting
Status indicators
Alarm signals
Inputs
Ambient probe
Evaporator probe
Door switch
High/low pressure switch
Kriwan® connection
Compressor functioning mode selection
Outputs
Compressor
Condenser fans output 1
Condenser fans output 2 (separated)
Evaporator fans
Defrosting heaters
Room light
Solenoid valve
Compressor oil heater
Aux1
Aux2
Supervision system
Control (4 HP):
TM
Code Numbers
Compressor motor circuit breaker range
4,5 – 6,3 A
7 – 10 A
TM
Control (7 HP):
Code Numbers
Compressor motor circuit breaker range
11 – 16 A
14 – 20 A
OPTYMA
Control (4 HP)
TM
400 x 300 x 135 mm
9 kg
IP 65
400 V AC ±10% 50/60Hz
3-phase
- 5 – 40 °C
-25 – 55 °C
from 30% to 95% RH
w/out condensate
< 1000 m
4 poles magnetothermic 16A "D"
Icn=6kA / Ics=8kA / Icu=15kA
Adjustable motor circuit breaker
Electrical
LED + display
LED + buzzer
NTC 10K 1%
NTC 10K 1%
Present
Present
Present
Pump-down / thermostat
See motor circuit breaker thermal
range relative to panel ID code
800 W (1 phase)
500 W (1 phase)
6000 W (AC1) eq. resistive load
800 W (AC1) resistive load
Present
Present
100 W
100 W
Modbus
OPTYMA
Control (7.5 HP)
TM
400 x 300 x 135 mm
10 kg
IP 65
400 V AC ±10% 50/60Hz
3-phase
- 5 – 40 °C
-25 – 55 °C
from 30% to 95% RH
w/out condensate
< 1000 m
4 poles magnetothermic 25A "D"
Icn=6kA / Ics=8kA / Icu=15kA
Adjustable motor circuit breaker
Electrical
LED + display
LED + buzzer
NTC 10K 1%
NTC 10K 1%
Present
Present
Present
Pump-down / thermostat
See motor circuit breaker thermal
range relative to panel ID code
800 W total
(1 phase)
2000 W (1phase / 3 phases)
9000 W (AC1) eq. resistive load
800 W (AC1) resistive load
Present
Present
100 W
100 W
Modbus
BC317523579312en-000101 | 3