Optyma
Plus
™
OP-LPQM, OP-MPXM
Name plate
OP-MPXM034MLP00G
A
114X4261
B
C
Application
MBP
D
Refrigerant
(1) R404A R507 R448A/R449A
R407A/R407F/R452A
E
M.W.P. HP
(1) 28 bar
M.W.P. LP
(1) 7 bar
F
Voltage
230 V ~ 1N ~ 50Hz
LRA
60 A
OIL INSIDE
POE 46
G
Serial No.
123456CG2816
xxxxxxxxxxxxxx
EAN No.
A: Model
B: Code number
C: Application, Protection
D: Refrigerant
E: Housing Service Pressure (Maximum
working pressure)
F: Supply voltage, Locked Rotor Ampere,
Maximum Current Consumption
G: Serial Number and bar code
Picture 2 : Stacked mounting
Picture 4 : Normal wiring
© Danfoss | DCS (CC) | 2020.12
MADE IN INDIA
Y
IP 54
(2) R134a
R513A
(2) 23 bar
(2) 5 bar
MCC 19 A
Picture 1 : Minimum mounting distances
Q: Air in
Danfoss A/S, 6430 Nordborg, Denmark
Unit
Housing 4
(Code n° 114X34-- or 114X44--)
V
U
V
T: Mounting brackets for stacked mounting (not supplied)
U: M8 bolts for stacked mounting (supplied)
V: Mounting bolts (not supplied)
Q
W
Z
R
X
R: Air out
W
X
Y
Z
[mm]
[mm]
[mm]
[mm]
250 900 700 700
T
U
Picture 5 : Temporary wiring
The condensing unit must only be used for
its designed purpose(s) and within its scope of
application.
Under all circumstances, the EN378 (or
other applicable local safety regulation)
requirements must be fulfilled.
The condensing unit is delivered under nitro-
gen gas pressure (1 bar) and hence it cannot
be connected as it is; refer to the «installation»
section for further details.
The condensing unit must be handled with cau-
tion in the vertical position (maximum offset
from the vertical : 15°)
Installation and servicing of the condensing
units by qualified personnel only.
Follow these instructions and sound
refrigeration engineering practice relating to
installation, commissioning, maintenance and
service.
Picture 3 : Electronic controller display
Compressor running
Crankcase heater on
Fan running
Temperature value for suction pressure.
Push lower button to switch to tempera-
ture value for condensing pressure
118A2221A - AN363632996019en-ZA0101 | 1