Section 11
Testing functionality by secondary injection
Table 31:
Test point
1
2
3
4
5
6
7
8
9
10
11
12
13
11.4.7.3
Measuring the operating limit of set values
Procedure:
1.
Subject the IED to healthy normal load conditions for at least two seconds.
2.
Apply the fault condition and slowly decrease the measured impedance to find the
operating value of the phase-to-phase fault for zone 1 according to test point 1 in figure
and table . Compare the result of the measurement with the set value.
3.
Repeat steps
Observe that the zones that are not tested have to be blocked and the zone that is tested
has to be released.
4.
Repeat steps
to figure and table .
122
Test points for phase-to-earth L3-E (Ohm/Loop)
Reach
Value
X
(2 x X1
+X0
set
R
0
X
(2 x X1
+ X0
set
R
(2 x R1
+ R0
set
X
0.8 x (2 x X1
R
0.8 x (2 x R1
+RFPEZx
X
0.5 x (2 x X1
R
0.5 x (2 x R1
RFPEZx
X
0.85 x RFPEZx x tan(ArgLd)
R
0.85 x RFPEZx
X
RLdFw x tan(ArgLd)
R
RLdFw
X
0
R
RLdFw
X
-0.8 x R
x tan( ArgDir)
min
R
0.8 x R
min
X
-0.4 x R
x tan( ArgDir)
min
R
0.4 x R
min
X
0.5 x (2 x X1
R
-0.5 x (2 x X1
tan( ArgNegRes-90⁰)
X
0.8 x (2 x X1
R
-0.8 x (2 x X1
tan( ArgNegRes-90⁰)
X
0.5 x (2 x X1
R
0.5 x (2 x R1
X
0
R
RFPEZx
1
to
2
to find the operating value for test points 2, 3 in table
1
to
3
to find the operating value for the phase-to-earth fault L3-E according
© Copyright 2017 Hitachi Power Grids. All rights reserved
Comments
)/3
set
)/3
set
)/3
set
+ X0
)/3
set
set
+ R0
)/3
set
set
+ X0
)/3
set
set
+R0
)/3 +
set
set
If RLdFw < 0.85 x RFPEZx
If RLdFw < RFPEZx
If RLdFw < RFPEZx
R
min
ArgDir = 15⁰ fixed
R
min
ArgDir = 15⁰ fixed
+ X0
)/3
ArgNegRes = 120⁰ fixed
set
set
Formula applies if R Set value < RFPEZx
+ X0
)/3 x
set
set
+ X0
)/3
ArgNegRes = 120⁰ fixed
set
set
Formula applies if R Set value < RFPEZx
+ X0
)/3 x
set
set
+ X0
)/3
set
set
+ R0
)/3
set
set
If RFPEZx < RLdFw
1MRK 505 378-UEN Rev. H
= minimum of RFPEZx and RLdFw
= minimum of RFPEZx and RLdFw
GUID-3FA4B640-38E7-406E-8FCC-8DEDABB024C4 v5
Line differential protection RED670
Commissioning manual