Switching time (OOT) ≤ 5 ms (OOT = Output Operating
Rated data of the output contacts
120 V ac
277 V ac
277 V ac
B300
R300
Anti-interference capacitors across the contacts
15.3 Insulation Test According to IEC 60255-27,
IEC 61010-1 and IEC 60870-2-1; Insulation rein-
forced; Category Cat. III
Voltage test (routine test) of
- auxiliary voltage
- binary inputs and relay outputs
Voltage test (routine test) of isolated
communi-cation ports only
- J (RS485)
- Z (Ethernet)
Impulse voltage test (type test) of all
process circuits (except for communication
ports) against the internal electronics
Impulse voltage test (type test) of all
process circuits against each other (except
for communication ports) and against the
PE terminal of class III
38
Time) additional delay of the out-
put medium used
5.0 A, GP
5.0 A, GP
0.7 HP
4.7 nF, ± 20 %, AC 250 V
Test
SICAM I/O Unit 7XV5673, Product Information
Test Values
DC 3.6 kV
AC 3.25 kV, 50 Hz
AC 500 V, 50 Hz
DC 700 V
6 kV (peak value);
1.2 µs/50 µs; 0.5 J;
3 positive and 3 negative
impulses at intervals of 1 s
5 kV (peak value);
1.2 µs/50 µs; 0.5 J;
3 positive and 3 negative
impulses at intervals of 1 s
E50417-B1050-C484-A3, Edition: 03.2012