Specification Of Power Supply Wire And Air Switch - Gree U-MATCH GUHD09NK3CO Service Manual

A/a dc inverter air conditioners t1/r410a/50hz
Hide thumbs Also See for U-MATCH GUHD09NK3CO:
Table of Contents

Advertisement

A/A DC INVERTER U-MATCH AIR CONDITIONERS

4.3 Specification of Power Supply Wire and Air Switch

Model
GUHD09NK3CO
GUHD12NK3CO
GUHD18NK3CO
GUHD24NK3CO
GUHD30NK3CO
GUHD36NK3CO
GUHD42NK3CO
GUHD48NK3CO
GUHD36NM3CO
GUHD42NM3CO
GUHD48NM3CO
GUHD60NM3CO
Note:
The parameters of the power cord listed above are only applicable to the BV single-core power cord which is laid
within the plastic bushing and used at 40℃, and those of the air switch are applicable to the one which also is used
at 40℃. If the actual installation conditions changes, please refer to the instructions of the power cord and the air
switch.
Capability of Air
Power
Switch(A)
Supply
(Outdoor/Indoor)
16/6
16/6
20/6
220-240V
20/10
32/10
50HZ
32/10
32/10
32/10
20/10
20/10
380-415V
3N~50Hz
20/10
20/10
Minimum Sectional
Minimum Sectional
Area
2
Of Earth Wire (mm
)
(Outdoor/Indoor)
2.5/1.0
2.5/1.0
4.0/1.0
4.0/1.5
6.0/1.5
6.0/1.5
6.0/1.5
6.0/1.5
4.0/1.5
4.0/1.5
4.0/1.5
4.0/1.5
INSTALLATION
Area
Of power Wire
2
(mm
)
(Outdoor/Indoor)
2.5/1.0
2.5/1.0
4.0/1.0
4.0/1.5
6.0/1.5
6.0/1.5
6.0/1.5
6.0/1.5
6.0/1.5
4.0/1.5
4.0/1.5
4.0/1.5
98

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents