Matching Form Of Power Cord And Air Switch - Gree JKFD5DQS/Na-E Service Manual

Table of Contents

Advertisement

following places:
① Water pipe; ② Gas pipe; ③ Blowing pipe;
④Other places that professional personnel consider unreliable.

7.2 Matching Form of Power Cord and Air Switch

Model
JKFD5DXXX(I)
JKFD5/Na-E(O)
JKFD7DXXX(I)
JKFD7XXX(I)
JKFD7/Na-E (O)
JKFD13XXX(I)
JKFD13/Na-M(O)
JKFD19XXX(I)
JKFD19/Na-M (O)
JKFD25XXX(I)
JKFD13//NaA-M
JKFD40XXX(I)
JKFD19//NaA-M
JKFD40/Na-M(O)
Note:
(1) Power cord of the unit must the cable with copper conductor and its working
temperature cannot exceed the designated value.
(2) If the power cord is longer than 15m, the cross sectional area shall be expanded
accordingly in case any accident caused by overloading.
ТОО "Everest climate", Р. К., г.Алматы | Телефон: +7 727 230 00 10, +7 777 250 10 90 | www.aircon.kz, e-mail: info@aircon.kz
GREE Air-ccoled Closed Control Unit Service Manual
Power Supply
220V ~ 50Hz
220V ~ 50Hz
220V ~ 50Hz
380V 3N~ 50Hz
220V ~ 50Hz
380V 3N~ 50Hz
220V ~ 50Hz
380V 3N~ 50Hz
220V ~ 50Hz
380V 3N~ 50Hz
220V ~ 50Hz
(O)
380V 3N~ 50Hz
220V ~ 50Hz
(O)
380V 3N~ 50Hz
Minimum Sectional
Air Switch
Capacity(A)
Earthed
Cable
40
-
63
32
-
32
-
40
-
63
-
100
-
-
41
2
Area(mm
Power
Cord
10
10
1
1
16
16
4
4
1
1
6
6
1.5
1.5
10
10
1.5
1.5
16
16
1.5
1.5
25
25
1.5
1.5
2.5
2.5