A/A DC INVERTER U-MATCH AIR CONDITIONERS
The installation shall be done by specialist technicians.

2.3 Caution for Installation

The outdoor unit shall be so installed that the air discharged out of the outdoor unit will not flow back and that
enough space shall be maintained around the machine for repair;
The installing position shall be in good ventilation, so that the machine can breathe and exhaust enough air.
Ensure that there is no obstruction at the inlet and outlet of the machine. If any, please remove the obstructions
blocking the air inlet and outlet.
If the outdoor unit is installed on concrete or solid ground, it shall be fixed by using M10 bolts and nuts. And
ensure that the machine is kept vertical and horizontal.
The outdoor unit must be lifted by using the designated lift hole. During lifting, take care to protect the air
conditioner and avoid knocking the metal parts, thus to prevent rusting in the future.
To meet the noise and vibration requirements, the outdoor unit shall be installed by using rubber damping pad
or spring damper.
To install the drainage pipe, please insert the drainage joint to the drainage hole on the outdoor chassis and
connect a drainage pipe on the drainage joint. (The installing height of outdoor unit shall be at least 5cm if
drainage joint is to be used).
To insert the pipe through the wall, the wall-cross tube must be installed.
The installing dimension shall comply with the installation requirements in these instructions. The outdoor unit
must be fixed at the installing position.
The installation shall be done by specialist technicians.
INSTALLATION
85