Recovery from Lockout
1. If the thermostat (controller) is still calling for heat one
hour after a lockout occurs, the control will automatically
reset and initiate a call for heat sequence.
2. The ignition control may also be manually reset,
removing power (24V) to IC terminal 24VAC for 5
seconds then restoring power.
LED Indications, Normal Operation
• Green, ½ sec ON, ½ sec OFF: Pre-purge, Inter-purge,
Post-purge
• Green, blinking rapidly: Trial for ignition
• Green, on solid: Flame detected, pilot/main burners on
Figure 81: HM/HD Series – SN Control (Staged Control)
BLK
Hot
L1
IGNITION CONTROL
BLK
BLK
L1
IND
BLU
AIR SWITCH -HI
GRY
APS-2
BLU
3
BLU
Customer
Interlocks
(See Note)
BLU
Factory
Jumper
BLU
BLU
BLU
5
GRY
BLU
LEGEND:
CUSTOMER PROVIDED COMPONENT
CUSTOMER / FIELD WIRING
INTERNAL TERMINAL CONNECTION
1
3
EXTERNAL TERMINAL CONNECTION
(2)
nd
2
ROLLOUT SWITCH ON HORIZONTAL BURNER TRAY ONLY
IM 777-18 • SKYLINE OUTDOOR AIR HANDLER
115 VAC
BLK
1
BLK
4
2
RED
CR1
IGNITION CONTROL
BLK
BLK
L1
IND
XFMR 1
WHT (Com)
BLK
40 VA
24V
YEL
COM
T1
24V
BLU
T2
GRY
T3
HAPS
T4
EST
J1
1/2
T5
Shunted
Br/W
BLU
R1
T6
T7
BLK
(-)
T8
E Valve
RED
BLU
BLU
(+)
T9
External Safety
Interlocks
YEL
3
T1
CR1
1
BLU
Br/W
Factory
24V SIG
Jumper
T' STAT
BLU
ORG
T2
T1
HI LIMIT
BLU
BLU
ORG
PUR
PUR
BLU
GRY
T-Stat
APS
24V
(PSW)
Series 5 Ignition Control
Sense
Gnd
Gnd
Syst.
5
(V2)
Alarm
MV
Spark
YEL
YEL
6
BLU
LO
2 STG GAS VALVE
GRY
HI
COM
Notes:
CUSTOMER PROVIDED COMPONENT
1.) If Customer safety interlocks provided,
wire in series from Terminal 3 to T1&
remove factory jumper
CUSTOMER / FIELD WIRING
INTERNAL TERMINAL CONNECTION
2.) Dip Switch setting for 0-10VDC Analog
1
EXTERNAL TERMINAL CONNECTION
3
Capable Controls – Series 5 Ignition Control
(2)
nd
2
ROLLOUT SWITCH ON HORIZONTAL BURNER TRAY ONLY
ERROR CODES - Red Flashes Error Definition Error Type
• 1 flash, then pause - No flame in trial time Lockout
• 2 flashes, then pause - Flame sense stuck on Lockout
• 3 flashes, then pause - Pilot/Main relay failure Lockout
• 4 flashes, then pause - Repetitive flame loss error
Lockout
• 5 flashes, then pause - Rollout error Lockout
• 6 flashes, then pause - APS Airflow error Lockout
• 7 flashes, then pause - Internal control error Lockout
• On Solid Red - Line Voltage/Frequency Error Standby
WHT
Neut
L2
115 VAC
DRAFT INDUCER
HI
WHT
LO
Not Used
RED
YEL
YEL
Maxitrol
SC40
WHT
BLK
See Notes for Dip
40VA
Switch Setting
R
24V
C
(+)
0 – 10 VDC Analag Iput
T11
(Polarity Sensitive)
(-)
T10
ORG
ROLL OUT
4
T' STAT
SWITCH
YEL
HI LIMIT
PUR
T2
3
YEL
PUR
ORG
PUR
T-Stat
24V
APS
ORG
(PSW)
Series 5 Ignition Control
Sense
ROLL OUT
ROLL OUT
Gnd
Gnd
SWITCH
SWITCH (2)
Syst.
ORG
MV
(V2)
Spark
Alarm
APS-1
YEL
YEL
AIR SWITCH -LO
WHT
FLAME
SENSOR
BLU
LO
SPARK
ROR
IGNITER
2 STG GAS VALVE
GRY
HI
COM
24VAC Alarm
Indicator
YEL
YEL
YEL
TIMER RELAY
ON
1 2 3 4
1/2
TR1 TIMER RELAY TERMINAL CONNECTION
Capable Controls – Series 5 Ignition Control
50
WHT
2
DRAFT INDUCER
WHT
3/4
YEL
ORG
YEL
ROLL OUT
SWITCH (2)
ORG
4
APS-1
AIR SWITCH -HI
YEL
WHT
FLAME
SENSOR
SPARK
ROR
IGNITER
24VAC Alarm
Indicator
YEL
YEL
TR1-090LH15
–
www.DaikinApplied.com
G
f
as
urnaCe