3.5.1 Power/Mains
The
DinBox RTU M4
Optional power backup, during/after a Mains disconnection, is provided via SuperCaps.
Power/Mains connection
Connect the ac mains or DC power supply to the power connector.
Make sure the voltage supplied to the
supply specification (see specifications above for details on voltage range).
SuperCap connection
The
DinBox RTU M4
SuperCap board with 4x Maxwell PC25 is directly soldered, via two wires, onto the main
PCB.
3.5.2 Ethernet Interface
The InduBox RTU M4 has a standard 10/100 Mbit/s Ethernet LAN interface.
This interface must be used to configure locally the RTU via the HTML GUI.
3.5.3 Configuration interface
Local communication with the
trace logging is done via the serial "configuration interface".
The RTU has a serial RS232 interface (RJ-45) which can be connected to a computer
or similar device via a RJ-45 to DB-9 serial cable. Only RxD, TxD, RTS and CTS are
used.
A terminal software program (eg. Windows HyperTerminal) must be used to
communicate with the RTU. The following parameters must be used :
Speed :
Data bits :
Parity :
Stop bits :
Flow control :
must be powered from mains or a DC power source (optional).
DinBox RTU M4
can optionally be delivered with a SuperCap backup. The
DinBox RTU M4
115.200 bps (default setting)
8
none
1
none
is in the range of the power
for configuration, setup, debugging and