8
8.1 Alarm list (read and reset)
IC200CX EVO
user manual
24
FUNCTION MENU
To access the functions menu, press and release the button. The list of functions can be
scrolled cyclically using the or buttons. Confirm access to the desired function with
the button.
After entering the functions menu, you will be able to do the following:
• View and reset the alarms present (ALrM)
• View and delete the alarm log (ALOG)
• Upload the parameter into the Hot Key (UPL)
• Enable – disable one or the two circuits (CrEn)
• Enable – disable one of the compressors (COEn)
• Read and reset the number of compressor running hour (Hour)
• Read and reset the number of compressor startsup (COSn)
• Read the compressor discharge temperature (COdt)
• Read the condensing fan speed percentage (Cond)
• Read the percentage of the proportional outputs (Pout)
• View time counting to next defrost cycle, under heat pump mode, (dF)
• Read the probe temperatures enabled to control the auxiliary output (uS)
• Read probe temperature of the remote panels VICX 620 (trEM)
• Read temperature, pressure, set point of the electronic expansion valve 1 (Et1)
• Read temperature, pressure, set point of the electronic expansion valve 2 (Et2)
• Enable – disable evaporator or condenser water pumps (PoEn)
Push or key to scroll the alarm list.
Push to reset the alarm (only with label "rSt" displayed, nothing happens when "no" label is
displayed)
The ALrM menu shows all the alarms present in the
unit. If the alarm is at automatic reset, the alarm
message will also be removed when the alarm is
terminated.
If the alarm is at manual reset, the alarm code and the
word "rst" or "no" will be displayed depending on
whether the alarm is resettable or not.