Electrical connection unit

Power supply

The power supply, including the safety switch, must be installed by a certified electrician.
Connect the unit to 3x400V+N+J.
See also the wiring diagram supplied with the unit.

Unit

The illustration shown is for a left-facing version:
Power supply (only for electric-heating surface, illustration shows without water-heating surface)
3x400V 50HZ
Safety switch
Safety switch
Power supply
3x400V 50HZ
Ampere consumption depending on selected compressor and fans:
Unit
Compressor*
MTZ
[Amp]
VPM 600
21
VPM 700
24
VPM 800
28
VPM 1000
31
VPM 1200
42
VPM 1500
54
VPM 2200
67
* Depending on MTZ / VTZ compressor (configuration dependent).
** Ampere consumption on fan motors depending on air volume and pressure loss. Calculated based on
nominal air volume at final pressure loss filter + external pressure loss = 500Pa and 1000Pa respectively
Fan (2 motors) total **
VTZ
at 500 Pa
[Amp]
[Amp]
21
4.0
24
4.4
30
6.3
36
8.3
44
8.2
58
10.5
72
20.5
VPM 600-2200 (English)
BY NILAN
at 1000 Pa
[Amp]
6.2
7.6
8.3
11.1
14.3
20.5
28.7
25