(H) Change the shift temperature in heating mode

If the indoor unit is installed at high location (ex. ceiling level), the thermostat tends to turn off at heating mode
because of the hot air temperature around ceiling level. In order to solve the problem, the shift temp. (valid
while heating only) is set when shipped from factory.
If the shift temp. is not enough (ex. the indoor unit is installed at position higher than 3 m), the shift temp. can
be set with remote controller from +1 to +10 deg. manually as follows:
a
Press the TEST / CHK button for more than 4 seconds.
3
b
In case of group control, if you want to change all units in group control collectively, proceed next step remaining
ALL displayed.
If you want to change a unit individually, select the indoor unit address (UNIT No.) with UNIT button.
c
Select the CODE No. 06 with
d
Choose the shift temp with
e
Press the SET button.
CODE No. 06, SET DATA and
f
If you made mistake, press the CL button.
g
Finally, press the TEST / CHK button.
AIR FLOW
UNIT
MODE
UNIT No.
R.C.
No.
FLAP
SET TEMP.
CODE
No.
TIMER SET
FAN SPEED
SETTING
SET
DATA
SET
CL
ON
OFF
TEST / CHK
,
(SET TEMP) button.
,
(
AIR FLOW
UNIT
MODE
UNIT No.
R.C.
No.
FLAP
SET TEMP.
CODE
No.
TIMER SET
SET TEMP.
FAN SPEED
SETTING
SET
DATA
SET
CL
ON
OFF
TEST / CHK
SETTING
0365_M_I
) button.
EX:
UNIT No. 1–6
CODE No. 06
Shift temp. +5 deg
0366_M_I
change from flashing to ON state.
III - 32
Service Procedures
SM830063