Section 5
Programming
Pressing the "Operating mode" key once takes the user from automatic operation to
Programming mode.
The upper display always shows the parameter and the lower one the set value. The
values are changed by pressing the é / ê keys. Subsequent pressing of the "ENTER" key
stores the value and takes the user to the next parameter.
To quit programming mode in any step, press the "Operating mode" key.
5.1. Program Menu
LANGUAGE SELECTION: This selects the language of the operating menu
(German, English, Spanish, French, Russian, Czech, Dutch, Polish,
Portuguese, Turkish)
1 I-CONVERTER PRIM: [ 5...13000]A
This selects the primary current of the current converter. Adjustment is
via the é / ê keys. Save and continue with ENTER
2 I-CONVERTER SEC:
This sets the secondary current of the current converter
Selection via é / ê. Save and continue with ENTER
3 END STOPP:
By setting the end stopp, the number of active capacitor branches is
matched to the respective capacitor bank. This is done via the é / ê
keys. The visible symbols of the capacitors correspond to the connected
outputs. The maximum possible number of capacitor branches is pre-
set at the works (6 branches).
Save and continue with ENTER
4 CONTROL SERIES:
The ratio of the capacitor branch power determines the control series,
the power of the first capacitor always being assigned the value 1. The
control series required for the compensation network is again selected
via the é/ê keys. If the required control series should exceptionally not
be present (Annex 1), the user may define a special one (control series
"E").More on this point in the control-series editor in Annex 1.
Save and continue with ENTER
5 CONTROL PRINCIPLE: The control preference may be selected here:
SEQUENTIAL connection
LOOP connection
INTELLIGENT loop connection (default setting)
COMBINED CHOKE
See Section 9 for an explanation of the various control modes.
Selection with é / ê keys. Save and continue with ENTER
[ 5 or 1]A
[ 1...6 ]
[ 1...20 + E ]
- 8 -
Prophi
6T
®
9

Advertisement

loading