Power factor controller

Advertisement

MANUAL MODE
STOPP C
1.00 IND
C1: AUTO (FIXED/TEST/OFF)
C2: AUTO (FIXED/TEST/OFF)
C3: AUTO (FIXED/TEST/OFF)
C4: AUTO (FIXED/TEST/OFF)
C5: AUTO (FIXED/TEST/OFF)
C6: AUTO (FIXED/TEST/OFF)
BACK TO 1
Changing
of values
by buttons:
Operating diagram (Brief programming)
Power Factor Controller Prophi-6T
SERVICE
1
min/max VOLTAGE
0 / 250.0 V
2 max REACTIVE POWER
88.88 kvar
3 max ACTIVE POWER
88.88 kW
4 max APPARENT PWR
88.88 kVA
5 max TEMPERATURE
40.0 °C
6
max VALUES
RESET [ NO ]
ERROR MEMORY
E [ 1 ] 08H ....
ERROR MEMORY
RESET [ NO ]
BACK TO 1
EXPERT MODE
1 PASSWORD ????
1 PASSWORD ????
[ 6343 ]
2 BASIC SETTINGS
EXPERT-MODE 2
NEW ? [ NO ]
3
SWITCH. POWER
Activation / Deactivation
max [25] kvar
of the following
error- messages is
possible with next steps
[ YES/NO ]:
4 TRIGGER VALUE
[ 66 ] %
- MEAS.VOLTAGE ?
- OVERVOLTAGE
- OVER COMPENSAT.
5
PROGRAM LOCK
- UNDERCOMPENSAT
[ NO ]
- HARMONICS
- OVERTEMPERATURE
- OVERCURRENT
6
PHASE I
- UNDERVOLTAGE
[ L1 ] - L1-N
- UNDERCURRENT
7
PHASE U
L1
- [ L1- N ]
8
POWER 1.STEP
2 ERROR ME.RELAY
[ 0...255 kvar ]
9
CONTROL
3
[ 3 ] PHASE
4
10
DISPLAY
[ COS PHI ]
11
HARMONICS
5
[ NO ]
Prophi
6T
®
[ 2244 ]
[ 120 ] sec.
UNDERVOLTAGE
[ 50 ] %
OVERVOLTAGE
[ 115 ] %
FREQUENCY
[ 40...80 Hz ]