Prophi
6T
®
Annex 2: Default settings
Note: The following values for the default settings apply only if the controller is supplied
directly from the manufacturer. Otherwise, these values may have been replaced by
settings made by the manufacturer of the compensation network (optimal values for the
relevant network).
No.
Parameter
0
LANGUAGE
1
I CONVERTER prim.
2
I CONVERTER sec.
3
END STOPP
4
CONTROL SERIES
5
CONTROL PRINCIPLE
6
POWER 1. STAGE
7
TARGET COS-PHI
8
MEASURING VOLTAGE
9
V- CONVERTER RATIO
SWITCH- IN TIME
10
11
SWITCH- OFF TIME
12
DISCHARGE TIME
13
ALARM TEMP.
DELAY ERROR MESSAGE
Capacitor stages
Password Expert mode 1
Password Expert mode 2
Trigger value
Max.simult.switch.power
Operating lock
Phase shift U/I
Power 1. stage
Control
20
Default setting
Programmed values of this
system (to be entered by
manufacturer or operator)
ENGLISH
1000 A
5 A
6
1
INTELLIGENT
25.00 kvar
0.98 IND
230 V L-N
- NO -
1 sec.
1 sec.
0.2 sec.
55 °C
20 sec.
AUTO
6343
Cannot be changed
2244
Cannot be changed
66%
4 x smallest stage
- NO -
0 °
0...255 kvar
3 - phase
- 19 -