Power factor controller

Advertisement

Prophi
6T
®
AUTO MODE
j
cos
0.76 IND
1
LINE VOLTAGE
230.0 V
2 APPARENT CURRENT
88.88 A
3 REACTIVE POWER
88.88 kvar
4
ACTIVE POWER
88.88 KW
5 APPARENT POWER
88.88 kVA
6
DIFF. TO PF
88.88 kvar
7
FREQUENCY
50.0 Hz
8
TEMPERATURE
25.0°C
9
HARMONICS [ 3.]
V:0.5% - I:0.5%
10
THD-V - THD-I
V 1.6% - I 0.9%
SOFTWAREVERSION
V 6.x - LCD
BACK TO 1
After 60 sec. without pressing
any button, automatic change
to auto-mode
22
PROGRAMMING
0
LANGUAGE
[ ENGLISH ]
1
I-CT PRIMARY
[ 1000 ] A / X
2
I-CT SECONDARY
1000 / [5] A
3
END STOPP 6
4 CONTROL SERIES 1
[1 1 1 1 1 1 ]
5
CONTROL MODE
[ INTELLIGENT ]
6
POWER 1.STAGE
[ 25 ]. 00 kvar
7
TARGET COS PHI
[ 0.98 ] IND
8
MEAS.VOLTAGE
[ 230 ] V L / N
9
V - CONVERTER
[ NO ]
10
SWITCH - IN TIME
[ 1000 ] ms
11
SWITCH - OFF TIME
[ 1000 ] ms
12
DISCHARGE TIME
[ 200 ] ms
13
ALARM TEMP.
[ 55 °C ]
27
DELAY A-MESS.
[ 20 ] sec
28
HARMONICS
THD-V
[ 7.0 ]%
BASIC SETTINGS
- NO -
BACK TO 1
only available if control
serie "E" is selected
CONTROL SERIES
EDITOR
KVAR-RATIO [ 1 ]
1
1
2 2 2 2
KVAR-RATIO [ 1 ]
1
1
2 2 2 2
KVAR-RATIO [ 2 ]
1
1
2 2 2 2
KVAR-RATIO [ 2 ]
1
1
2 2 2 2
up to last capacitor
KVAR-RATIO [ 2 ]
1
1
2 2 2 2
BACK TO 1
Changing
of values
by buttons:

Advertisement