Prophi
6T
®
Section 4 Automatic operation - display of network parameter
The controller is set to automatic operation as standard. Capacitor stages are then
automatically connected in or out in order to reach the target power factor. This happens
when the required reactive power exceeds the value of the smallest capacitor stage.
In automatic operation, various network parameters can be displayed by repeatedly
pressing the "ENTER" key:
Action
Display
ENTER
1 LINE VOLTAGE
ENTER
2 APPARENT CURRENT
ENTER
3 REACTIVE POWER
ENTER
4 ACTIVE POWER
ENTER
5 APPARENT POWER
ENTER
6 DIFF. kVAR TO TARGET COS
ENTER
7 FREQUENCY
ENTER
8 TEMPERATURE
ENTER
9 HARMONICS (3.-19.)
ENTER
10 THD-V; THD-I
ENTER
Software version
ENTER
Return to: 1
The power value specifies the total power (3-phase) assuming symmetrical load. If no
key is pressed for 60 seconds, the display automatically returns to the operating status!
Switching outputs
The switching outputs are executed as
transistor outputs.
The transistor outputs are used via an
additional auxiliary voltage (10 - 24 VDC) for
a direct triggering of thyristor switches for the
dynamic power factor correction (i.e. TSM).
Max.current for a single output: 40mA
Sum current all 6 outputs: 150mA
!
WARNING: Mixing-up of outputs and thus applying of 230 VAC on
the transistor outputs will destroy the internal transistors !
8
1 LINE VOLTAGE
230.1 V
in V
in A
in kvar
in kW
in kVA
in Hz
in °C
V/%, I/%
in%
- 7 -
/ %
/ %
/ %
/ %
/ °F
Block circuit of the transistor output
X2:1
to thyristor module
( e.g. TSM-LC...)
X2:2
Further stages
X2:6 (12)
J
X2:P 200mA
+
-
E.g. 24VDC