janitza Prophi 6T Manual page 10

Power factor controller

Advertisement

Prophi
6T
®
6 POWER 1. STAGE:
To determine the controller's response sensitivity, the dimensions of the network's
smallest capacitor (stage 1) must be known. They are entered in two steps in kvar.
The integral kvar values (before the comma) are initially selected via the é / ê
keys and saved with ENTER. The positions after the comma are then selected,
again via the é / ê keys. If the response sensitivity is being undercut, a warning
will occur ( indication of "!" in the display )
Save and continue with ENTER
7 TARGET COS PHI:
By setting the target cos phi, the power factor to be attained via the PF correction
is defined. It is also set via the é / ê keys.
Save and continue with ENTER
8 MEASURING VOLTAGE
Programming the measuring voltage. The values programmed here always refer
to the voltage at the clamps of the device!
The voltage is selected via the é /ê keys. Save and continue with ENTER.
9 V - CONVERTER RATIO
When a measuring-voltage converter (e.g. for HV- measurement) is used, its
conversion ratio should be programmed here:
- Direct programming of the prim. voltage of the voltage converter
-
- The sec. voltage is set automatically from the programmed meas.voltage under 8
Selection via the é /ê keys. Save and continue with ENTER.
meas.current
Im (X/1A)
L1 (R)
L2 (S)
L3 (T)
Im
10 CONNECTING TIME
This refers to the time between connecting the capacitors to increase the
momentary network capacitance. It should be noted that in practical operation the
real connection time is affected by the discharge time (locking time).
Default setting:
Selection is performed via the é /ê keys. Continue with ENTER
10
[ 0.01 ... 255.99 ] kvar
[ 0.3 ind ... 0.3 cap ]
[ 30 ... 525] V
[ NO ]
HV - voltage
20 kV / 400 V
20000
100
P P r r o o p p h h i i - - 6 6 T T
[ 20...1000]ms
1000 ms
- 9 -
possible: 230V...380kV / Vmeas.
meas.-
supply-
voltage
voltage
Vm
Vb
Vm
Vb
L1 (R)
L2 (S)
L3 (T)
N
PE