Digital Outputs - ABB PQFS Installation, Operation And Maintenance Instructions

Power quality filter
Table of Contents

Advertisement

Figure 45: Cabling of the alarm status of a multi-unit filter consisting of masters only, using the
In the
Figure 45
Both master units are in alarm OR
The external 24 V power supply fails OR
Both filter units are disconnected from the supply.

6.12.2.2 Digital outputs

A second method to implement the alarm functionality is to use the PQF-Manager's
programmable digital output contacts. Use this approach when the condition for alarm
is uniquely defined, e.g. an alarm has to be given only when the filter trips due to an
unacceptably high network voltage or when the filter trips due to a well-defined internal
error. This type of alarm has to be cabled on the 8 pin terminal block situated at the top
right corner when looking at the PQF-Manager from the rear (Cf.
The digital output contacts have a common point (cabled on contacts 1 and 2) and are
of the NO-type (normally open). The contact ratings are:
Maximum continuous ac rating: 440 Vac/1.5 A.
Maximum continuous dc rating: 110 Vdc/0.3A.
The common is rated at 9 A/terminal, giving a total of 18 A.
When using a power supply of 24Vdc, a minimum current of 10 mA should be
drawn by the circuit connected to the digital output contact.
Table 25
shows the status of a digital output contact configured as alarm contact for
different operation modes of the filter.
Table 25: Status of a digital output contact configured as alarm contact for different
Filter state
Disconnected from the supply
Filter (auxiliaries) connected to
the supply, no error present
62 Electrical design and installation  Manual Power Quality Filter PQFS
NO Alarm
contact of
master 1
+
24 Vdc
external
supply
NO Alarm
contact of
master 2
-
Note: Contacts drawn in non-alarm position
NO alarm contact on each filter.
above, the external input will be low if:
filter operation modes
Normally open digital contact state
Open
Open
External
digital
input
Figure
39).

Advertisement

Table of Contents
loading