ABB PQFS Installation, Operation And Maintenance Instructions page 58

Power quality filter
Table of Contents

Advertisement

stop command to the filter too. This section gives an example of how the cabling has to
be done on the filter side.
Any of the two digital inputs on the PQF-Manager (Cf.
the remote control functionality. The electrical requirements of the digital inputs are
given in
Table 63
implement the remote control functionality on Digital Input 1.
Figure 41: Implementation of remote control functionality on Digital Input 1 of
WARNING: If a function is assigned to a digital input, the same function must never be
assigned to the other digital input. Otherwise the filter may behave erratically.
Once the cabling has been finished:
The auxiliary fuse box may be closed
The filter top cover may be replaced including the connection of the
PQF-Manager to the master unit
The power to the filter may then be restored
Then, the PQF-Manager has to be used to associate the remote control functionality with
Digital Input 1. This is done by going to the digital input setup menu and selecting
'Remote ON' for digital input 1. When this is done the filter will switch on when the switch
S shown in
Figure 41
Refer to
Section 7.9.1.4
In a multi-master arrangement, the master that has the control over the system (i.e. the
master which is operational and which has the lowest address) will monitor the digital
inputs. Therefore, in order to obtain full redundancy with filters consisting of more than
58 Electrical design and installation  Manual Power Quality Filter PQFS
(Filter characteristics section).
Switch controlled
by external process
S
+
24 Vdc
external
power
(b)
supply
-
Remarks:
(a)
Left hand terminal block when looking from rear, counting from top to bottom
(b)
Acceptable power supply range: 15Vdc-24 Vdc, driving current 13mA@24Vdc
the PQF-Manager
is closed and the filter will switch off when the switch S is opened.
for guidelines on how to navigate to the digital input setup menu.
Figure
39) can be used to cable
Figure 41
gives an example of how to
PQF-Manager
+
(a)
Digital input 1
1
(15-24Vdc)
2
(a)
-