Implementing a bypass connection
If bypassing is required, employ mechanically or electrically interlocked contactors between
the motor and the drive and between the motor and the power line. Make sure with
interlocking that the contactors cannot be closed simultaneously. The installation must be
clearly marked as defined in IEC/EN 61800-5-1, subclause 6.5.3, for example, "THIS
MACHINE STARTS AUTOMATICALLY".
Bypass connection is available as a factory-installed option for certain cabinet-built drive
types. Consult ABB for more information.
WARNING!
Never connect the drive output to the electrical power network. The connection
may damage the drive.
Protecting the contacts of relay outputs
Inductive loads (relays, contactors, motors) cause voltage transients when switched off.
The relay contacts on the drive control unit are protected with varistors (250 V) against
overvoltage peaks. In spite of this, it is highly recommended that inductive loads are equipped
with noise attenuating circuits (varistors, RC filters [AC] or diodes [DC]) to minimize the
EMC emission at switch-off. If not suppressed, the disturbances may connect capacitively
or inductively to other conductors in the control cable and form a risk of malfunction in other
parts of the system.
Install the protective component as close to the inductive load as possible. Do not install
protective components at the relay outputs.
Electrical planning guidelines 39