Note: ** for Emax series, the protection unit contains an internal communication unit (when required). Connections between various units, depending on the scenario (Master or Slave mode are shown as indications only, the specific cabling must be carried out according to official ABB SACE documentation. Scenario remote supervision “Master mode”...
Operating environmental temperature: -5 °C ... +70 °C Storage conditions: -40 °C ... +90 °C 2.4. Communication Bus Exclusive ABB SACE communication bus (internal bus) 2.5. Internal relay characteristics Type Monostable Maximum switching capacity 150 W / 1250 VA (resistive load)
Fast flashing Flashing with freq. = 2Hz see *** *** Flashing at 2Hz one of the following can be verified: Communication not present SACE PR010/K in stand-by mode or Self-test Connected protection unit not recognised Rev. Apparatus Sh. No. SACE PR010/K L0633 Mod.
• Any LED state which does not conform with the above probably indicates a malfunction of the SACE PR010/K unit. • The indications given in the above table are with Vaux present, and with the PR010/K not in Self-test, and not in stand-by mode (see par.5.3).
5.2. Connections Carefully study the relevant electrical diagram for the wiring of the connectors. For the dedicated inputs and outputs, wiring other than that described in the official ABB SACE electrical diagrams is not allowed Rev. Apparatus Sh.
1 = Matching signalling of selected using the dip-switches is not provided, in this case the event B event associated with each contact is unique (defined by ABB SACE), and is independent of the position of the dip-switch (0 or1).
Off (0) On (1) PR010/K Top view Dip-switches for setting of functioning mode. 5.3.2. Default settings The PR010/K unit is supplied by ABB SACE with the following parameters pre-set: Description of Value set Dip-Sw n° dip-switch Test Off (Deactivated)
5.4. SACE PR010/K with SACE PR112 unit (with last letter of serial number A…E) 5.4.1. Dip-switch settings N° Description of 0 (Off) 1 (On) Note Dip-Sw dip-switch For normal functioning mode, set this dip-switch to Test Normal Self-test OFF. Not used Configuration Master if PR112/P + PR010/K.
5.5. SACE PR010/K with SACE PR112 unit (with last letter of serial number F…Z) 5.5.1. Dip-switch settings N° Description of 0 (Off) 1 (On) Note Dip-Sw dip-switch For normal functioning mode, set this dip-switch to Test Normal Self-test OFF. K51/4...
5.6. SACE PR010/K with SACE PR113 unit 5.6.1. Dip-switch settings N° Description of 0 (Off) 1 (On) Note Dip-Sw dip-switch For normal functioning mode, set this dip- Test Normal Self-test switch to OFF. K51/1 Alarm Pre-alarm function if dip-switch N°5 = Off...
5.6.3. Connection of 3 SACE PR010/K units with SACE PR113/P It is possible to connect two or three SACE PR010/K units with a PR113/P unit (see par. 5.9.2). The only condition being that one PR010/K unit must be configured as Master, with the other(s) configured as Slave.
5.7. SACE PR010/K with SACE PR212/P unit 5.7.1. Dip-switch settings N° Description of 0 (Off) 1 (On) Note Dip-Sw dip-switch Test Normal Self-test For normal functioning mode, set this dip-switch to OFF. Not used Master if PR212/P + PR010/K Mode...
5.8. SACE PR010/K with SACE PR212/MP unit 5.8.1. Dip-switch settings N° Description of 0 (Off) 1 (On) Note Dip-Sw dip-switch For normal functioning mode, set this dip-switch to Test Normal Self-test OFF. K51/4 Function U Protection WC Protection Functions (A or B)
Before consulting the following table, check the LEDs on the front panel of the PR010/K unit for several seconds. (wait until the end of the start up phase if the unit has just been switched on). • FN indicates normal functioning. Rev. Apparatus Sh. No. SACE PR010/K L0633 Mod. Apparecchio N° Pag. Doc. No. Sh. No ÿþþ...
Note the type of load connected to the signalling unit (lamps, signalling relays, CBs, contacts, sirens etc..) and the serial number of the unit (see par.5.3.3). Send / communicate all the information, along with applicable electrical diagrams, to the nearest ABB SACE Service centre.