9.2
RF650R/RF680R/RF685R error messages
Note that if there are error messages, the error LED ("ER") of the reader flashes. You can
read out the error using the XML or STEP 7 block error codes. As an alternative, you can
also recognize the error using the LED status display of the RF680R and RF685R readers
as described in the section "How the LED status display works (Page 401)".
The following table lists only the STEP 7 block error codes specific to the RF680R/RF685R.
Table 9- 2
Error messages of the RF650R, RF680R and RF685R readers
"ER"
XML/
S7 block
LED
LED
(hex)
(hex)
2 Hz
0x11
0xE1FE01
2 Hz
0x12
0xE1FE02
2 Hz
0x13
0xE1FE03
2 Hz
0x1A
0xE1FE0A
2 Hz
0x91
0xE1FE81
2 Hz
0x92
0xE1FE82
2 Hz
0x93
0xE1FE83
2 Hz
0x94
0xE1FE84
2 Hz
0x95
0xE1FE85
2 Hz
0x22
0xE2FE02
2 Hz
0xA1
0xE2FE81
2 Hz
0xA2
0xE2FE82
2 Hz
0xA3
0xE2FE83
2 Hz
0xA4
0xE2FE84
2 Hz
0xA5
0xE2FE85
SIMATIC RF600
System Manual, 10/2016, J31069-D0171-U001-A19-7618
Error description
Memory of the transponder cannot be written to
Transponder memory is defective.
Transponder EEPROM was written too frequently and has reached the end of its ser-
vice life
Presence error
The transponder is no longer within the transmission window of the reader. The command
was not or only partially executed.
Read command: There is no valid data in "IDENT_DATA".
Write command: The transponder that has just left the antenna field contains an incomplete
data record.
Possible causes:
Operating distance between reader and transponder is not being maintained.
Configuration error: The data record to be processed is too large (in dynamic mode).
Address error
The address area of the transponder has been exceeded.
Possible causes:
Start address of the command start has been incorrectly set.
Wrong transponder type
The area to be written to is write-protected.
The transponder is read/write-protected.
The transponder is not responding.
The transponder password is incorrect. Access is denied.
The verification of the written transponder data has failed.
General transponder error
The transponder has too little power to execute the command.
More transponders are located in the transmission window than can be processed at the
same time by the reader.
There is no transponder with the required EPC-ID in the transmission window or there is no
transponder at all in the antenna field.
The requested data is not available.
The transponder signals a CRC error.
The selected antenna is not enabled.
The selected frequency is not enabled.
9.2 RF650R/RF680R/RF685R error messages
System diagnostics
403