Hints for design
_____________________________________________________________________________________________
Ordering
_____________________________________________________________________________________________

Technical data

Siemens Building Technologies SpA
Respect current regulations for wiring. The devices should be directly connected to mains
(that is with no switches, etc.) and be permanently powered up.
The positive logic operation of internal relay means an always energized contact (C-NC
open) in no alarm and/or fault condition.
EV control output is solid state type and is sized for an INTELLIGAS
valve with 13W maximum absorbed power. It is not to be used to drive solenoid
valves with higher power consumption.
Indicate control unit number and sensor corresponding to the gas type to be detected
LYC11
Gas detection control unit for 1 sensor
QAG13/A
Sensor IP44 for Methane detection (CH4)
QAG13.P/A
Sensor IP44 LPG detection
QAO13/A
Sensor IP44 for carbon monoxide (CO) detection
Control unit LYC11
Power supply voltage
Frequency
Power consumption
Control Outputs
Operation Logic
type of controlled solenoid valve
(see data sheet n° 7684).
Connections length
Cable cross section
Connectable sensor
Optical indications
Timers
Allowed room temperature
Allowed room humidity
Case
Protection
Dimensions
compliance
Regulations
Standards
24VAC +/-10%
50 Hz
21VA max (with battery under charge)
- electronic 12V DC (13W max)
- SPDT Relay 250V 5(3)A
Positive (normally energized relay, de-energizes in case of alarm
and/or fault)
normally closed type E..D / E...DFL or
normally open type E...E
80m max (sensor and NO solenoid valve)
40m max (NC solenoid valve)
2
1.5mm
min (sensor and solenoid valve)
1 (type QA..13/A)
Green LED (power presence / TEST)
Yellow LED (control unit / solenoid valve / sensor fault)
Red LED (gas alarm)
3s between alarm acknowledgement from sensor and solenoid valve,
relay output and relevant LED activation.
0...+50°C (operation)
-20...+70°C (transport and storage)
20...90% R.H. non condensing
PC polycarbonate
IP20 – EN60529
130 x 106 x 56.5 mm
Low voltage
Electromagnetic Compatibility
EN60335-1
EN50270
®
solenoid
73/23 CEE
89/336 CEE
CE1N7601e 05-04-2004
6/8