TSI MEDIA - 230VAC User Manual V7.3 BEYOND THE INVERTER THE NEW GENERATION OF POWER CONVERTERS DUAL INPUT INVERTER Commercial Power as default source AC BACKUP IN A DC ENVIRONMENT Leverage your existing DC infrastructure ONE STOP SHOP Wide output power range...
9.1.1 Prerequisites............................19 9.1.2 Surge suppression ..........................20 9.1.3 Terminations ............................20 9.1.4 Grounding ............................. 20 9.1.5 DC Input ............................... 20 9.1.6 AC Input ..............................21 9.1.7 AC Output ............................. 21 – TSI Media 230 Vac– User manual – v7.3...
Page 3
15.4 By-pass to Normal ............................40 15.5 Manual by-pass >20kVA ..........................41 15.5.1 Normal to By-pass ..........................41 15.5.2 By-pass to Normal ..........................41 16. Finishing .................................. 42 17. Commissioning ................................ 43 – TSI Media 230 Vac– User manual – v7.3...
Page 4
21.1 Cabinet foot print, layout ........................... 48 21.2 Single phase circuit diagram ..........................49 21.3 Three phase circuit diagram ..........................50 21.4 Mains connection, single phase ........................51 21.5 Mains connection, three phase ......................... 52 – TSI Media 230 Vac– User manual – v7.3...
Page 5
Release Note: Release date Modified Version Modifications (DD/MM/YYYY) page number 02/05/2013 First release of the Manual. 13/11/2013 Amendment and correction. 18/01/2016 Amendment and correction. 02/11/2016 Amendment and correction. – TSI Media 230 Vac– User manual – v7.3...
Maintenance free Battery friendly CE+T power puts 60+ years expertise in power conversion together with worldwide presence to provide customized solutions and extended service 24/7 - 365. – TSI Media 230 Vac– User manual – v7.3...
When handling the system/units pay attention to sharp edges. * These instructions are valid for most CE+T Products/Systems. Some points might however not be valid for the product described in this manual – TSI Media 230 Vac– User manual – v7.3...
Earthing must be carried out prior to energizing the system. Earthing shall be made according to local regulations. 3.3.3 Other Isolation test (Hi-Pot) must not be performed without instructions from the manufacturer. – TSI Media 230 Vac– User manual – v7.3...
If the equipment is dismantled, to dispose of its component products, you must comply with the local regulations in force in the country of destination and in any case avoid causing any kind of pollution. To download the latest documentation and software, please visit our website at www.cet-power.com. – TSI Media 230 Vac– User manual – v7.3...
Information and data given in this chapter is intended to serve as an overview of the TSI Technology. Detailed features and parameters for each individual module type in the range may differ and should be referred to in the dedicated data sheet. – TSI Media 230 Vac– User manual – v7.3...
Start, control and exit are fully automatic. A specific example of Mix-mode is the Walk-in mode where the transfer from DC source to AC source is ramped up within a fixed and adjustable period of time. – TSI Media 230 Vac– User manual – v7.3...
Telecom / Datacom: -48 VDC / 230 VAC, 50/60 Hz The TSI MEDIA is a 1500 VA / 1200 W triple port inverter. All versions available in EPC or REG. The TSI inverter modules are hot swappable and hot pluggable.
Recording of the latest 200 events. Fi-Fo 3 outgoing alarms 2 digital inputs MOD bus CAN bus USB front connector – TSI Media 230 Vac– User manual – v7.3...
WARNING IF AN ATS (automatic transfer switch) IS INSTALLED UPSTREAM, MAKE SURE THAT IT DOES NOT ALLOW TRANSFER BETWEEN AC SOURCES OUT OF SYNC. THE MAXIMUM ALLOWED PHASE SHIFT IS 10°. – TSI Media 230 Vac– User manual – v7.3...
OF/SD Up to 40 A 6.3.2 MCCB AC output distribution via MCCB in the range up to 400 A (1p, 2p or 3p). Max two MCCB per inverter cabinet. – TSI Media 230 Vac– User manual – v7.3...
Display Backlit 2 line dot matrix. The display shows two values simultaneously. 7.1.2 TCP/IP Agent The TCP/IP interface board is mounted on the CanDis shelf and is powered within the system. – TSI Media 230 Vac– User manual – v7.3...
Seamless transfer (0 ms) between primary and secondary source of supply. No single point of failure. Flexible AC output distribution. Full modularity. Full redundancy. – TSI Media 230 Vac– User manual – v7.3...
Wire all positions in the sub-rack for future expansion. Input AC / Output AC / Input DC / Signal cables shall be separated. Cable crossings shall be done in at 90° angles. – TSI Media 230 Vac– User manual – v7.3...
PE Chassis ground shall be wired to MET or distributed earth bar connected to MET, according to local regulations. 9.1.5 DC Input CB per module Cable, min Connector Torque -48 VDC 40 A 2 x 6 mm 5 Nm – TSI Media 230 Vac– User manual – v7.3...
Digital input characteristics (Digital In 1 / 2) Signal voltage +5 VDC (galvanically insulated) ln 1 Digital 1 Max wire size 1 mm Common ln 2 Digital 2 – TSI Media 230 Vac– User manual – v7.3...
AC Input (Green) DC Input (Green) Open Closed Normal operation All (Green) Closed Closed Normal operation All (Green) Warning: If remote ON/OFF not used, pin 2 and 3 MUST be bridged together! – TSI Media 230 Vac– User manual – v7.3...
Remove material using a pair of side-cutters to allow cable entry and exit. The rear cover is ordered separately. Connect cables Cut holes to allow cable access Clip rear cover into place – TSI Media 230 Vac– User manual – v7.3...
If you prefer to take the wooden crate apart before raising the cabinet, make sure you do not damage or dent the cabinet while doing so. Warning: The top cover fixing bolts must NEVER be replaced with lifting eye bolts. – TSI Media 230 Vac– User manual – v7.3...
Input AC / Output AC / Input DC / Signal cables shall be separated. Cable crossings shall be made at 90° angles. Empty inverter positions shall be covered with blanked off. – TSI Media 230 Vac– User manual – v7.3...
The top cover accommodates nylon tie straps used to strap the cables. DC Input Cables Input & Output AC Input & Output Top Plate - Type I Top Plate - Type II Top Plate - Type III – TSI Media 230 Vac– User manual – v7.3...
The three phase input is 123, ABC, RST phase sensitive; clockwise rotation is recommended. Phase one starts at 0° phase shift, while the other phases will be at -120° phase shift and + 120° phase shift resulting in three phase output. – TSI Media 230 Vac– User manual – v7.3...
Note: Screws and nuts are not included in the delivery. M12 holes. Internal DC distribution with circuit breakers (Q01-Q32) per inverter module. Max 3 x 240 mm per pole (group). – TSI Media 230 Vac– User manual – v7.3...
Page 29
Note: Screws and nuts are not included in the delivery. M6 holes for positive bus bar per connection. Max 35 mm per connection terminal. – TSI Media 230 Vac– User manual – v7.3...
- Max wire size 1 mm 10.4.8.2 Digital In (X5) Input characteristics X5 (Digital In 1, Digital In 2) - Signal voltage +5 VDC (galvanically insulated) - Max wire size 1 mm – TSI Media 230 Vac– User manual – v7.3...
Page 32
Initial system start must be performed with an operational T2S. If the T2S is missing at start-up the modules will fail to start. The following sequence of the Remote ON/OFF will force the system to start without the T2S. #3 ==> #2 ==> #3 will force the modules to start. – TSI Media 230 Vac– User manual – v7.3...
- Urgent 60 seconds delay - Non urgent 30 second delay USB port Parameter setting via Laptop or Copy/Paste. Factory default according to list of set values. – TSI Media 230 Vac– User manual – v7.3...
Read T2S manual for detailed setup. 12.1 Communication settings Bits per second 9600 Data bits Parity None Stop bits Flow control None – TSI Media 230 Vac– User manual – v7.3...
0 > Return to previous menu 1 > System actions 0 > Return to index 1 > Turn ON system 2 > Turn OFF system 3 > Change Date and time setting – TSI Media 230 Vac– User manual – v7.3...
Page 36
1 > Force refresh of configuration texts and constants 2 > Force refresh of events description texts 4 > Security Access 0 > Return to index 1 > Enable Password protection – TSI Media 230 Vac– User manual – v7.3...
A) Slide the module in B) Push firmly till the connection is C) Close the cover and latch the module properly engaged in place if too hard redo step B – TSI Media 230 Vac– User manual – v7.3...
Replace front, make sure that the front latches properly. Plug in. Check fan for operation. Access T2S and reset the fan run time alarm from within the action menu. – TSI Media 230 Vac– User manual – v7.3...
A wide range of breakers is used. Delivered breakers may vary from the example shown in the picture. Make sure that the breaker is in OFF position. Connect load cables to the terminal. Switch the breaker ON. – TSI Media 230 Vac– User manual – v7.3...
15.4 By-pass to Normal Switch DC ON. Turn switch to INTERMEDIATE (mid position). PAUSE: Wait until the inverter modules reach full operation and have synchronized (30-60 seconds). Complete twist to ON. – TSI Media 230 Vac– User manual – v7.3...
15.5.1 Normal to By-pass 0 1 1 0 1 0 15.5.2 By-pass to Normal 0 1 PAUSE: Wait until the inverter modules reach full operation and have synchronized (30-60 seconds). 0 1 1 0 – TSI Media 230 Vac– User manual – v7.3...
Cover empty inverter positions with blanks. Make sure that the Remote ON/OFF is wired appropriately for local regulations. Make sure that the point of AC supply meets local regulations. – TSI Media 230 Vac– User manual – v7.3...
Installation and commissioning must be done and conducted by trained people fully authorized to do so. Performing any isolation test is prohibited without instructions from the manufacturer. Equipment is not covered by warranty if procedures are not respected. – TSI Media 230 Vac– User manual – v7.3...
Switch OFF AC input (commercial power failure) and check the alarm according to the configuration Switch OFF DC input (DC power failure) and check that the alarm according to the configuration Check the different digital input according to the configuration (when used) – TSI Media 230 Vac– User manual – v7.3...
Check that the RJ45 cable is connected between T2S shelf and CanDis shelf No value on TCP/IP: Check that the RJ45 cable is connected between T2S shelf and CanDis shelf Wait approximately 2 minutes to allow the system to collect serial data. – TSI Media 230 Vac– User manual – v7.3...
With an infrared camera check termination hot spots - Tighten terminations 19.4 Manual By-Pass If mains failure occurs during operation, the load is lost Perform a manual by-pass operation – TSI Media 230 Vac– User manual – v7.3...
Be aware that products shipped back to CE+T Power without being registered first will not be treated with high priority! (Label shown here is only for representation). – TSI Media 230 Vac– User manual – v7.3...
Appendix 21.4 Mains connection, single phase TN - C - S (400/230VAC) TN - S (400/230VAC) TT (400/230VAC) TN - C (400/230VAC) – TSI Media 230 Vac– User manual – v7.3...
Appendix 21.5 Mains connection, three phase TN - C - S (400/230VAC) TN - S (400/230VAC) TN - C (400/230VAC) TT (400/230VAC) – TSI Media 230 Vac– User manual – v7.3...