Dual input inverter, the commercial power as default source, ac backup in a dc environment, leverage your existing dc infrastructure, one stop shop, wide output power range, harshest ac input conditions, without compromising the quality of the ac output, (51 pages)
Page 3
Release Note: Release date Modified Version Modifications (DD/MM/YYYY) page number 27/06/2018 First release of the Manual 07/12/2018 Amendment and correction 21/11/2019 New layout – e-one 10 - 48/230 - User manual - v1.2...
CE+T at a glance 1. CE+T at a glance CE+T Power designs, manufactures and markets a range of products for industrial operators with mission critical applications, who are not satisfied with existing AC backup systems performances, and related maintenance costs.
2. Abbreviations Regular Digital Signal Processor Alternating current Direct current Electro Static Discharge Main Earth Terminal Universal Serial Bus Protective Earth (also called Main Protective Conductor) Neutral Printed Circuit Board – e-one 10 - 48/230 - User manual - v1.2...
• Local regulations must be adhered. * These instructions are valid for most CE+T Products/Systems. Some points might however not be valid for the product described in this manual. – e-one 10 - 48/230 - User manual - v1.2...
Min Class I + Class II or combined Class I+II. 3.3 Other • Isolation test must not be performed without instructions from the manufacturer. To download the latest documentation and software, please visit our website at www.cet-power.com – e-one 10 - 48/230 - User manual - v1.2...
Description 4. Description e-one 10 - 48/230 is a compact inverter providing a pure sine wave 230 V AC supply from 48 V DC input. Additionally AC input is featured for bypass operation. e-one 10 - 48/230 comes with a IEC Socket at front and protected with a fuse.
Page 9
EN61000-4-5 Surge criteria B all ports EN61000-4-6 class A criteria A 10V * This specification is valid for DC mode only. In By-pass mode, the output will be same as AC input. – e-one 10 - 48/230 - User manual - v1.2...
Installation 5. Installation e-one 10 - 48/230 is designed for installation in an IP20 environment. When installed in a dusty or humid environment, appropriate measures should be taken. The module is foreseen to be recessed into an electrical cabinet of 19” and 1U height standard or wall mounted.
Step B: Place the e-one module inside the 19” cabinet horizontally and fix with M6 screws. 5.3.2 Wall mounting Step A: Fix the brackets on both sides of the e-one module with M3 screws. – e-one 10 - 48/230 - User manual - v1.2...
Before any intervention on the e-one input, operator has to make sure that power is switched off on DC leads and AC input mains. Some safety labels are stuck on the unit. It should not be removed. – e-one 10 - 48/230 - User manual - v1.2...
DC breaker Cable size Max size 40 VDC 1 x 6 mm² e-one 10 - 48/230 22 A* 25 A 4 mm² per pole * Recommended upstream protection: minimum 30 A – e-one 10 - 48/230 - User manual - v1.2...
Page 14
Also the core should be near to the module. Tube Ferrite: 22.3 x 10.3 x 10.3 AL = 20.5uH +/- 30% VNF EMC “TDG TS13 (T22 x 10 x 10)” AC Input Module Side – e-one 10 - 48/230 - User manual - v1.2...
Page 15
The Fuse Holder automatically ejects from the slot. (Fuse holder will not go beyond 45°). Step 2. Remove the Fuse holder from the slot. Step 3. Replace the appropriate new Fuse in the holder. – e-one 10 - 48/230 - User manual - v1.2...
N.B. : relays are energized while idle (i.e. relays de-energized when event occur). MAJOR relay provide an open or close free potential contact Relay characteristics: • Maximum switching capacity: 1 A @ 60 VDC • Maximum switching power: 30 W – e-one 10 - 48/230 - User manual - v1.2...
Page 17
Installation 5.4.4.2 Remote ON/OFF e-one 10 - 48/230 system can be remotely activated or stopped (stand-by mode). Changeover contacts must be used. To turn off the Inverter remotely, both conditions “Pin 1-3, Closed” and “Pin 2-3, Open” must be met.
Inverter overloaded output unavailable Permanent ORANGE (Load transfer to BYPASS) 6.2.2 Lamp Status S. NO AC OUT Lamp Description Voltage present at output terminal Voltage is not present at output terminal – e-one 10 - 48/230 - User manual - v1.2...
• Make sure that DC IN polarity is according to marking. • Make sure that AC IN phase and neutral connections are according to marking • Re tighten all electrical terminations. • Switch ON DC breaker. – e-one 10 - 48/230 - User manual - v1.2...
If the equipment is dismantled, to dispose of the products it consists of, you must stick to the local regulations in force in the country of destination and in any case avoid causing any kind of pollution. – e-one 10 - 48/230 - User manual - v1.2...
Installation and commissioning must be done and conducted by trained people fully authorized to act on installation. It is prohibited to perform any isolation test without instruction from manufacturer. Equipments are not covered by warranty if procedures are not respected. – e-one 10 - 48/230 - User manual - v1.2...
Check if inverters are working properly (INFO LED Green) Check if inverter is working in By pass mode Check output voltage Check if system has no alarm Switch OFF system Test on load (if available) – e-one 10 - 48/230 - User manual - v1.2...
Check front ON/OFF button and Remote ON/OFF terminal Inverter only run on AC or DC: Check the Voltage range for DC or AC and AC Frequency range No output power: Check the front AC Output Fuse – e-one 10 - 48/230 - User manual - v1.2...
Maintenance shall only be performed by properly trained people. 11.1 Manual check • Measure input voltage (DC input, AC output) with multi-meter • Replace dust filter (if present) • Take a snap shot of the inverter – e-one 10 - 48/230 - User manual - v1.2...
• The RMA number should be mentioned on all shipping documents related to the repair. • Be aware that products shipped back to CE+T Power without being registered first will not be treated with high priority! (Label shown here is only for representation)