Design compressor mounting
General requirements
Single requirements
24
AB237586440343en-000601
Compressors used in single applications must be
mounted with flexible grommets.
All compressors are delivered with four rubber
grommets and metal sleeves. Compressors
must always be mounted with these grommets.
Recommended torque for mounting bolts: 11 Nm
(±1 Nm).
During operation, the maximum inclination from
the vertical plane must not exceed 7 degrees.
1.7
29.5
41
5/16" - 18 UNC
self tapping
Ø11
Ø 41
Recommended torque for
mounting bolts: 11 Nm (±1 Nm)
Not supplied
with grommet