Application Guidelines VZH088-117-170 single compressors VZH scroll specificities ......................5 Inverter compressors ......................6 Compressor size ......................................6 Frequency converter variants ................................. 6 Compressor and frequency converter combinations ........................6 Nomenclature and specifications ..................7 Compressor nomenclature ..................................7 Frequency converter nomenclature ..............................7 Technical specifications .......................
Page 4
Application Guidelines VZH088-117-170 single compressors Operating conditions ......................41 Application envelopes .....................................41 Short cycle timer function ..................................41 Discharge gas temperature protection function ...........................42 Discharge gas thermostat ..................................42 Oil return management function (single compressor) ........................43 Oil return management in hybrid manifolding ..........................43 High and low pressure protection...............................43 System design recommendations ..................45 Essential piping design considerations .............................45...
Application Guidelines VZH scroll specificities Reinforced high grade cast iron scroll set. 2 ranges for high and low pressure ratio High speed oil circulation minimized by separating oil and gas flows with a sump oil return tube A patented oil injection system ensures optimal efficiency at low speed by improving scroll set sealing...
Application Guidelines Inverter compressors Compressor size Inverter technology offers more flexibility 3. Best Seasonal Efficiency Ratio: Select a in compressor selection than fixed speed compressor size which achieves the minimum compressors. Selection of the right inverter system cooling demand at its minimum speed. compressor size can be done by different Ensure that the compressor is able to cover the methods:...
Application Guidelines Nomenclature and specifications Compressor nomenclature Variable speed Evolution index Motor protection type Family N: no internal motor protection VZH scroll (protection by drive) Lubricant Equipement version POE lubricant, R410A A: brazed connections, single version refrigerant B: brazed connections, manifold version Oil sight glass Oil level switch Swept volume...
VZH088 Rotolock 1"3/4 used when compressors are mounted in parallel. VZH117 Rotolock 1"3/4 Contact Danfoss for further details and refer to VZH170 Rotolock 2"1/4 the VZH hybrid manifold guideline (FRCC.PC.049). Oil drain fitting VZH170 are equipped with oil drain connection.
Application Guidelines Dimensions CDS303 frequency converter - enclosure B1 380-480 Volts - 15 kW - IP55 housing scale 1:2 Min 100 Air space outlet Air outlet Min 100 Air space inlet Air inlet Mounting base scale 1:2 FRCC.PC.023.A8.02...
Page 29
Application Guidelines Dimensions CDS303 frequency converter - enclosure B2 380-480 volts – 18-22 kW - IP55 housing Min 200 Ø19 Air space outlet Scale 1:2 outlet inlet Min 200 Mounting base Air space inlet Scale 1:2 FRCC.PC.023.A8.02...
Page 30
Application Guidelines Dimensions CDS303 frequency converter - enclosure B3 380-480 volts - 15 kW - IP20 housing Ø12 Scale 1:2 Min 200 Air space outlet Air outlet Mounting base Min 200 Air inlet Air inlet Scale 1:2 FRCC.PC.023.A8.02...
Page 31
Application Guidelines Dimensions CDS303 frequency converter - enclosure B4 380-480 volts – 18-22 kW - IP20 housing 200-240 volts - 15 kW - IP20 housing 525-600 volts - 18-30 kW - IP20 housing Min 200 air space outlet Scale 1:1 outlet inlet Min 200...
Page 32
Application Guidelines Dimensions CDS303 frequency converter - enclosure C1 200-240 volts – 15-18-22 kW - IP55 housing scale 1:2 Min 200 Air space outlet Air outlet Min 200 Mounting base Air inlet Air space inlet scale 1:2 FRCC.PC.023.A8.02...
Application Guidelines Electrical data, connections and wiring Supply voltage Because VZH compressors are powered by a When having a supply of 230V, 380V or 460V the frequency converter, the mains frequency, 50 or following coefficients must be applied: 60 Hz, is no longer an issue. Only the mains = 0.87* I voltage is to be taken into account.
Application Guidelines Electrical data, connections and wiring Fuses / circuit breakers Danfoss recommends using the fuses/circuit and are recommended. Other types of circuit breakers listed below to protect service breakers may be used provided they limit the personnel and property in case of component energy to a level equal to or lower than the break-down in the frequency converter.
Application Guidelines Electrical data, connections and wiring Wire sizes Below table lists recommended wiring sizes for the motor compressor power supply cables. These wiring sizes are valid for a cable length up to 20 m. from drive to from network to compressor to drive From network to frequency converter From frequency converter to compressor...
Application Guidelines Electrical data, connections and wiring EMC correct installation of an IP20 frequency drive CDS303 EMC qualification reports are available upon request to Danfoss technical support. PLC etc. Panel Grounding rail Cable insulation stripped Min. 0.025 in ² (16 mm²)
Application Guidelines Electrical data, connections and wiring Wiring connections T1/U T2/V T3/W Ana out COM Ana out + Ana out +10 V 230V or 24V Ana in 0 ± 10 V ~ Ana in 0 ± 10 V 2 A max Ana in COM +24V +24V...
Application Guidelines Electrical data, connections and wiring Electrical connections Electrical power is connected to the compressor The cable gland has to be of EMC design to terminals by Ø 4.8 mm (3/16") screws. The garanty a good grounding of the armored cable. maximum thightening torque is 3 Nm.
Application Guidelines Operating conditions Application envelopes The operating envelopes for VZH scroll • To avoid liquid floodback, oil sump superheat compressors are given in the figures below, should also be taken care of. Please refer to where the condensing and evaporating “liquid floodback during operation”...
Application Guidelines Operating conditions Discharge gas A discharge temperature monitor function can be To activate the discharge temperature monitor temperature protection enabled in the frequency converter. All settings function, with the factory setting, the only function are available in parameter list 28.2x, they are modification required is to connect the sensor factory preset as follow: to Analog Input 54 (4 - 20 mA) between 13 and...
Insulation Bracket A DGT accessory is available from Danfoss: refer to accessories pages at the end of this document. Oil return management Insufficient oil level can be the result of oil rpm (50 rps) for too long (as programmed in function (single depositing itself in pipes and heat exchangers.
Page 44
(except with pump-down). Danfoss recommend to use ETS products. EXV should be closed, and remained closed, Ramp-up and ramp-down settings, of both EXV and compressor, must be done with great care.
Application Guidelines System design recommendations Essential piping design The working pressure in systems with R410A is drops and acceptable minimum gas velocities, considerations about 60% higher than in systems with R22 or the refrigerant piping must be reduced in size R407C.
In order to prevent compressors from breaking piping (long line set, U trap…), multiple heat down due to oil level issues, Danfoss requires the exchangers and elevation changes. use of an oil separator in all long piping systems, particularly for split systems.
Page 47
(Orifice Φ2.0) code number 018F6257 “24V (CE)” 50Hz AC” specification 1m 3-core cable solenoil coil code number 018F6282 “220-230V 50/60Hz AC” specification 1m 3-core cable Customers can of course contact Danfoss application engineers for support regarding recommendations in such systems. FRCC.PC.023.A8.02...
In this respect, follow the More detailed information can be found in the guidelines given in the section: “Essential piping paragraphs hereafter. Please contact Danfoss design recommendations” in priority. technical support for any deviation from these guidelines.
Application Guidelines System design recommendations Crankcase heater / sump heater: When the A crankcase heater is only effective if capable of compressor is idle, the oil temperature in the sustaining this level of temperature difference. sump of the compressor must be maintained Tests must be conducted to ensure that the at no lower than 10 K above the saturation appropriate oil temperature is maintained under...
12 K above the reaches a satisfactory level. ambient temperature for air cooled condensers. Note: The minimum condensing pressure must For further information, please contact Danfoss be set at the minimum saturated condensing Technical support. temperature shown in the application envelopes.
Application Guidelines Specific application recommendations An oversized valve may result in erratic control. • The compressors should be run for a This can lead to liquid refrigerant entering the minimum period in order to ensure that the compressor if the expansion valve does not oil has sufficient time to properly return to provide stable refrigerant super-heat control the compressor sump and that the motor has...
Page 52
Application Guidelines Specific application recommendations Discharge temperature Heat pumps frequently utilize high condensing temperatures. Operating the compressor at monitoring temperatures in order to achieve a sufficient too high discharge temperatures can result temperature rise in the medium being heated. in mechanical damage to the compressor as At the same time, they often require low well as thermal degradation of the compressor evaporating pressures to obtain sufficient...
4 way valve components recommendations, in particular 4 moving. way valve Max. Operating Pressure Differential. Danfoss recommend above defrost cycle logic, Opening degree and time have to be set in order but the control logic is also system specified. Suction line accumulator...
Acoustic hoods are available from Danfoss as accessories. These hoods are quick Use of sound-insulation materials on the inside of and easy to install and do not increase the overall unit panels is an effective means of substantially size of the compressors to a great extend.
Application Guidelines Installation Each compressor is shipped with printed http://instructions.cc.danfoss.com instructions for installation. These instructions can also be downloaded from: Compressor handling Each VZH scroll compressor is equipped with When the compressor is mounted as part of an installation, never use the lift rings on the two lift rings on the top shell.
For servicing of existing installations where acid formation is present the Danfoss DCL solid core filter driers containing activated alumina are recommended. Brazing and soldering...
For specific applications not covered herein, please contact Danfoss for further information. High voltage test On M Ohm 2000 M Ohm 200 2000MOhm M ohm...
The best location is on the Refer to news bulletin FRCC.EN.050 “Danfoss liquid line between the condenser outlet and the Commercial Compressors recommended filter drier.
If any deviation is observed, this means that some oil is trapped in the system, heat exchangers and/or pipes. Always use original Danfoss POE oil 160SZ from new cans. The CDS303 frequency converter integrates an oil recovery management algorithm which needs Top-up the oil while the compressor is idle.
Setting Error(s) cable Check VZH Come back to Motor resistance factory settings and isolation Correct Incompatibility the fault Between Software & Mains shut-off Additional option before checking ! Contact your Local Danfoss Reset & start March, 2014| Commercial Compressors FRCC.PC.023.A8.02...
Page 61
Check main power supply Check power voltage supply voltage Power normal Set 14-11 to lower value Internal components damage Too high or Reset & start too low Contact your Local Danfoss Turn off power Reset & start March, 2014| Commercial Compressors FRCC.PC.023.A8.02...
Page 62
Application Guidelines Troubleshooting Check alarm # (Continue) Start failed Speed limit (low) Wrong wiring of U/V/W Minimum speed not reached after 2 sec. Compressor bearing wear Compressor stopped, similar reason as A49 Compressor stopped Automatic restart after 30s Automatic restart after 30s 10 restarts before blockage...
Application Guidelines Ordering information and packaging Kit ordering and shipping The tables on the following pages give code compressor and CDS303 frequency converter kit numbers for ordering purposes for the VZH packed and shipped separately. Packaging Compressor single pack Height Width Depth Weight...
Page 64
Application Guidelines Ordering information and packaging X = Motor code Compressors industrial pack Compressor model Technical Name Code G Code J VZH088AXANA 120G0078 120G0080 VZH088BXANA 120G0079 120G0081 VZH088 VZH088AXBNA 120G0090 120G0092 VZH088BXBNA 120G0091 120G0093 VZH117AXANA 120G0082 120G0084 VZH117BXANA 120G0083 120G0085 VZH117 VZH117AXBNA 120G0094...
Application Guidelines Ordering information and packaging VZH voltage code G - 380-480 Volt Frequency converter Compressor model Code n° for Model & power IP class RFI class Coating ordering 134G3576 134G3577 IP20 134F9366 134G3578 CDS303 VZH088-G 15.0kW 134G4008 134G4010 IP55 134G4012 134G4013 134G3579...
Application Guidelines Ordering information and packaging VZH voltage code J - 200-240 Volt Frequency converter Compressor model Code n° for Model & power IP class RFI class Coating ordering 134G3474 IP20 134F9361 134X1964 CDS303 VZH088-J 15.0kW 134G4001 IP55 134G4002 134G3585 IP20 134F9363 134X1965...
Application Guidelines Accessories Mounting kits Type Code n° Description Application Packaging Pack size Mounting kit for 1 scroll compressor including 4 120Z0066 VZH088-117 Single pack grommets, 4 sleeves, 4 bolts, 4 washers Mounting kit for 1 scroll compressor including 4 8156138 VZH170 Single pack...
Page 69
Application Guidelines Accessories Fans Type Code n° Description Application Packaging Pack size 130B3406 Fan IP55 VZH117 G & J Single pack Control card Type Code n° Description Application Packaging Pack size 130B5667 Control card Frequency converter / all models Single pack Accessory bags Type Code n°...
Page 70