Configuring/address space

4.2 Reaction to CPU STOP

GSD file
The respective GSD file for the ET200SP Distributed I/O System can be downloaded from
the Internet:
● GSD file PROFINET IO (http://support.automation.siemens.com/WW/view/en/57138621)
● GSD file PROFIBUS DP
PROFIBUS DP is not supported.
4.2
Reaction to CPU STOP
In the case of a CPU STOP, an active charging process is aborted after three seconds. This
means the PWM signal on the CP connection switches to "-12 V" (EVSE status not
available). The associated contactor (DQx output) and the corresponding ACTx output are
disabled. In this case, the lock is automatically unlocked (even if the "LockActive" bit is set).
Breakdowns in communication, such as an interruption of the PROFINET connection, are
treated as CPU STOPs.
4.3

Required I/O address space

Address space of the technology module
Table 4- 2
Range
Further information
You can find a description of the control and feedback interface of the SIMATIC ET 200SP
TM ECC 2xPWM ST technology module in the section Control and feedback interface
(Page 35).
32
Range of the I/O addresses of the SIMATIC ET 200SP TM ECC 2xPWM ST technology
module
Inputs
16 bytes
Technology module TM ECC 2xPWM ST (6FE1242-6TM10-0BB1)
Outputs
8 bytes
Manual, 04/2018, A5E42681298B-AA